OEM High Quality Power Circuit Breaker Manufacturer – CC1 Series AC Contactor for 9-95A – Changan Group
OEM High Quality Power Circuit Breaker Manufacturer – CC1 Series AC Contactor for 9-95A – Changan Group Detail:
Description
Application: remote making & breaking circuits; protect circuit from over-load when assembling with thermal over-load relay; frequent start-up and control of AC contactor;
Electric value: AC50/60Hz, 690V, up to 95A; Utilization category: AC-3, AC-4;
Altitude: ≤2000m;
Ambient temperature: -5℃~+40℃; Mounting category: Ⅲ;
Mounting conditions: inclination between the mounting plane and the vertical plane should not exceed ±5°;
Standard: IEC/EN 60947-4-1. IEC/EN 60947-5-1.
Control Coil Voltage(AC Coil Operation)
Volts(VAC) |
24 |
36 |
42 |
48 |
110 |
127 |
220 |
230 |
240 |
380 |
415 |
440 |
480 |
500 |
600 |
|
Code |
50Hz |
B5 |
C5 |
D5 |
E5 |
F5 |
G5 |
M5 |
P5 |
U5 |
Q5 |
N5 |
R5 |
- |
S5 |
Y5 |
60Hz |
B6 |
- |
D6 |
E6 |
F6 |
G6 |
M6 |
- |
U6 |
Q6 |
- |
R6 |
T6 |
- |
- |
|
50/60Hz |
B7 |
- |
D7 |
E7 |
F7 |
- |
M7 |
P7 |
- |
Q7 |
N7 |
R7 |
- |
- |
- |
Control Coil Voltage(DC Coil Operation)
Volts(VDC) |
12 |
24 |
36 |
48 |
110 |
220 |
Code |
JD |
BD |
CD |
ED |
FD |
MD |
Technical Specification
Standard | IEC/EN60947-4-1 IEC/EN60947-5-1 | |||||
Model No. |
CC1-09 |
CC1-12 |
CC1-18 |
CC1-25 |
CC1-32 |
|
Rated Conventional Heating Current |
Ith (A) |
20 |
20 |
32 |
40 |
50 |
Rated Voltage Ui(V) |
Ui(V) |
690 |
690 |
690 |
690 |
690 |
Rated Operation CurrentUe=380/415V |
AC-3 Ie(A) |
9 |
12 |
18 |
25 |
32 |
AC-4 Ie(A) |
3.5 |
5 |
7.7 |
8.5 |
12 |
|
Power Controlled 3ph cage MotorAC-3 |
220/240V KW |
2.2 |
3 |
4 |
5.5 |
7.5 |
380/415V KW |
4 |
5.5 |
7.5 |
11 |
15 |
|
660/690V KW |
5.5 |
7.5 |
10 |
15 |
18.5 |
|
Electrial life(x103 operations) |
AC-3 |
1000 |
1000 |
1000 |
1000 |
800 |
AC-4 |
200 |
200 |
200 |
200 |
200 |
|
Mechanical life(x106 operations) |
10 |
10 |
10 |
10 |
8 |
|
Matched Fuse |
Size |
RT16-00 |
RT16-00 |
RT16-00 |
RT16-00 |
RT16-00 |
A |
20 |
20 |
32 |
40 |
50 |
|
Main circuit |
3P or 4P |
|||||
Auxiliary circuit Cat.:AC-15,Ue=415V Ie=0.95A Ith=10A | 1NO or 1NC |
Standard | IEC/EN60947-4-1 IEC/EN60947-5-1 | |||||
Model No. |
CC1-40 |
CC1-50 |
CC1-65 |
CC1-80 |
CC1-95 |
|
Rated Conventional Heating Current |
Ith (A) |
60 |
80 |
80 |
100 |
125 |
Rated Voltage Ui(V) |
Ui(V) |
690 |
690 |
690 |
690 |
690 |
Rated Operation CurrentUe=380/415V |
AC-3 Ie(A) |
40 |
50 |
65 |
80 |
95 |
AC-4 Ie(A) |
18.5 |
24 |
28 |
37 |
44 |
|
Power Controlled 3ph cage MotorAC-3 |
220/240V KW |
11 |
15 |
18.5 |
22 |
25 |
380/415V KW |
18.5 |
22 |
30 |
37 |
45 |
|
660/690V KW |
30 |
33 |
37 |
45 |
45 |
|
Electrial life(x103 operations) |
AC-3 |
800 |
600 |
600 |
600 |
600 |
AC-4 |
150 |
150 |
150 |
100 |
100 |
|
Mechanical life(x106 operations) |
8 |
8 |
8 |
6 |
6 |
|
Matched Fuse |
Size |
RT16-00 |
RT16-00 |
RT16-00 |
RT16-00 |
RT16-00 |
A |
63 |
80 |
80 |
100 |
125 |
|
Main circuit |
3P or 4P |
|||||
Auxiliary circuit Cat.:AC-15,Ue=415V Ie=0.95A Ith=10A |
1NO+1NC |
Model |
Cabling cross section(Cu) |
screw size | Tightening torque(N.m) | |||
Number of piece |
Flexible cable with cold-pressed socket(mm2 ) |
Flexible cable without cold- pressed socket(mm2 ) |
Inflexible cable(mm2 ) | |||
CC1-09 |
1~2 |
2.5 |
4 | 4 |
M3.5 |
0.8 |
CC1-12 |
1~2 |
2.5 |
4 | 4 |
M3.5 |
0.8 |
CC1-18 |
1~2 |
4 |
6 | 6 |
M3.5 |
0.8 |
CC1-25 |
1 |
4 |
10 | 6 |
M4 |
1.2 |
2 |
4 |
6 | 6 |
M4 |
1.2 |
|
CC1-32 |
1 |
4 |
10 | 6 |
M4 |
1.2 |
2 |
4 |
6 | 6 |
M4 |
1.2 |
|
CC1-40 |
1 |
10 |
16 | 10 |
M4 |
3.5 |
2 |
10 |
10 | 10 |
M8 |
3.5 |
|
CC1-50 |
1 |
16 |
25 | 25 |
M8 |
3.5 |
2 |
16 |
16 | - |
M8 |
3.5 |
|
CC1-65 |
1 |
16 |
25 | 25 |
M8 |
3.5 |
2 |
16 |
16 | - |
M8 |
3.5 |
|
CC1-80 |
1 |
50 |
50 | 50 |
M8 |
3.5 |
2 |
25 |
35 | - |
M10 |
4.0 |
|
CC1-95 |
1 |
50 |
50 | 50 |
M10 |
4.0 |
2 |
25 |
35 | - |
M10 |
4.0 |
1.L: in main circuit, the distance between terminals and plate;
2.P: in main circuit, the distance between two phases;
3.S: in main circuit, the width of contacting plate.
Model |
A max |
B max |
C max |
D max |
E max |
a |
b |
Φ |
L |
P |
S |
CC1-09(Z)~12(Z) |
47 |
76 |
82(116) |
120.5(154.5) |
140.5(174.5) |
34/35 |
50/60 |
4.5 |
60(95) |
10.5 |
8.6 |
CC1-18(Z) |
47 |
76 |
87(122) |
125.5(160.5) |
145.5(180.5) |
34/35 |
50/60 |
4.5 |
61(96) |
11.3 |
10.4 |
CC1-25(Z) |
57 |
86 |
95(131) |
133.5(169.5) |
153.5(189.5) |
40 |
48 |
4.5 |
70(107) |
13.2 |
11.7 |
CC1-32(Z) |
57 |
86 |
100(138) |
138.5(176.5) |
158.5(196.5) |
40 |
48 |
4.5 |
71.6(120) |
14.5 |
13 |
CC1-4011(Z)~6511(Z) |
77 |
129 |
116(173) |
154.5(211.5) |
174.5(231.5) |
40 |
100/110 |
6.5 |
78(135) |
20 |
8.6 |
CC1-4004/4008(Z)~6504/6508(Z) |
84 |
129 |
116(173) |
154.5(211.5) |
174.5(231.5) |
40 |
100/110 |
6.5 |
78(135) |
20 |
8.6 |
CC1-8011(Z)~9511(Z) |
87 |
129 |
127(188) |
165.5(226.5) |
185.5(246.5) |
40 |
100/110 |
6.5 |
83(140) |
23.5 |
12 |
CC1-8004/8008(Z)~9504/9508(Z) |
96 |
129 |
127(183) |
160.5(221.5) |
180.5(241.5) |
40 |
100/110 |
6.5 |
83(140) |
23.5 |
12 |
Product detail pictures:
Related Product Guide:
We've numerous great employees customers excellent at promoting, QC, and working with kinds of troublesome difficulty inside the generation method for OEM High Quality Power Circuit Breaker Manufacturer – CC1 Series AC Contactor for 9-95A – Changan Group , The product will supply to all over the world, such as: Turkey, Porto, Pretoria, With a fully integrated operation system, our company has won a good fame for our high quality products, reasonable prices and good services. Meanwhile, we have established a strict quality management system conducted in material incoming, processing and delivery. Abiding by the principle of "Credit first and customer supremacy", we sincerely welcome clients from home and abroad to cooperate with us and advance together to create a brilliant future.
By Miguel from Portugal - 2017.11.20 15:58
The company account manager has a wealth of industry knowledge and experience, he could provide appropriate program according our needs and speak English fluently.
By Amelia from Germany - 2018.12.28 15:18