Description
Application: remote making & breaking circuits; protect circuit from over-load when assembling with thermal over-load relay; frequent start-up and control of AC contactor;
Electric value: AC50/60Hz, 690V, up to 95A; Utilization category: AC-3, AC-4;
Altitude: ≤2000m;
Ambient temperature: -5℃~+40℃; Mounting category: Ⅲ;
Mounting conditions: inclination between the mounting plane and the vertical plane should not exceed ±5°;
Standard: IEC/EN 60947-4-1. IEC/EN 60947-5-1.
Control Coil Voltage(AC Coil Operation)
Volts(VAC) |
24 |
36 |
42 |
48 |
110 |
127 |
220 |
230 |
240 |
380 |
415 |
440 |
480 |
500 |
600 |
|
Code |
50Hz |
B5 |
C5 |
D5 |
E5 |
F5 |
G5 |
M5 |
P5 |
U5 |
Q5 |
N5 |
R5 |
- |
S5 |
Y5 |
60Hz |
B6 |
- |
D6 |
E6 |
F6 |
G6 |
M6 |
- |
U6 |
Q6 |
- |
R6 |
T6 |
- |
- |
|
50/60Hz |
B7 |
- |
D7 |
E7 |
F7 |
- |
M7 |
P7 |
- |
Q7 |
N7 |
R7 |
- |
- |
- |
Control Coil Voltage(DC Coil Operation)
Volts(VDC) |
12 |
24 |
36 |
48 |
110 |
220 |
Code |
JD |
BD |
CD |
ED |
FD |
MD |
Technical Specification
Standard | IEC/EN60947-4-1 IEC/EN60947-5-1 | |||||
Model No. |
CC1-09 |
CC1-12 |
CC1-18 |
CC1-25 |
CC1-32 |
|
Rated Conventional Heating Current |
Ith (A) |
20 |
20 |
32 |
40 |
50 |
Rated Voltage Ui(V) |
Ui(V) |
690 |
690 |
690 |
690 |
690 |
Rated Operation CurrentUe=380/415V |
AC-3 Ie(A) |
9 |
12 |
18 |
25 |
32 |
AC-4 Ie(A) |
3.5 |
5 |
7.7 |
8.5 |
12 |
|
Power Controlled 3ph cage MotorAC-3 |
220/240V KW |
2.2 |
3 |
4 |
5.5 |
7.5 |
380/415V KW |
4 |
5.5 |
7.5 |
11 |
15 |
|
660/690V KW |
5.5 |
7.5 |
10 |
15 |
18.5 |
|
Electrial life(x103 operations) |
AC-3 |
1000 |
1000 |
1000 |
1000 |
800 |
AC-4 |
200 |
200 |
200 |
200 |
200 |
|
Mechanical life(x106 operations) |
10 |
10 |
10 |
10 |
8 |
|
Matched Fuse |
Size |
RT16-00 |
RT16-00 |
RT16-00 |
RT16-00 |
RT16-00 |
A |
20 |
20 |
32 |
40 |
50 |
|
Main circuit |
3P or 4P |
|||||
Auxiliary circuit Cat.:AC-15,Ue=415V Ie=0.95A Ith=10A | 1NO or 1NC |
Standard | IEC/EN60947-4-1 IEC/EN60947-5-1 | |||||
Model No. |
CC1-40 |
CC1-50 |
CC1-65 |
CC1-80 |
CC1-95 |
|
Rated Conventional Heating Current |
Ith (A) |
60 |
80 |
80 |
100 |
125 |
Rated Voltage Ui(V) |
Ui(V) |
690 |
690 |
690 |
690 |
690 |
Rated Operation CurrentUe=380/415V |
AC-3 Ie(A) |
40 |
50 |
65 |
80 |
95 |
AC-4 Ie(A) |
18.5 |
24 |
28 |
37 |
44 |
|
Power Controlled 3ph cage MotorAC-3 |
220/240V KW |
11 |
15 |
18.5 |
22 |
25 |
380/415V KW |
18.5 |
22 |
30 |
37 |
45 |
|
660/690V KW |
30 |
33 |
37 |
45 |
45 |
|
Electrial life(x103 operations) |
AC-3 |
800 |
600 |
600 |
600 |
600 |
AC-4 |
150 |
150 |
150 |
100 |
100 |
|
Mechanical life(x106 operations) |
8 |
8 |
8 |
6 |
6 |
|
Matched Fuse |
Size |
RT16-00 |
RT16-00 |
RT16-00 |
RT16-00 |
RT16-00 |
A |
63 |
80 |
80 |
100 |
125 |
|
Main circuit |
3P or 4P |
|||||
Auxiliary circuit Cat.:AC-15,Ue=415V Ie=0.95A Ith=10A |
1NO+1NC |
Model |
Cabling cross section(Cu) |
screw size | Tightening torque(N.m) | |||
Number of piece |
Flexible cable with cold-pressed socket(mm2 ) |
Flexible cable without cold- pressed socket(mm2 ) |
Inflexible cable(mm2 ) | |||
CC1-09 |
1~2 |
2.5 |
4 | 4 |
M3.5 |
0.8 |
CC1-12 |
1~2 |
2.5 |
4 | 4 |
M3.5 |
0.8 |
CC1-18 |
1~2 |
4 |
6 | 6 |
M3.5 |
0.8 |
CC1-25 |
1 |
4 |
10 | 6 |
M4 |
1.2 |
2 |
4 |
6 | 6 |
M4 |
1.2 |
|
CC1-32 |
1 |
4 |
10 | 6 |
M4 |
1.2 |
2 |
4 |
6 | 6 |
M4 |
1.2 |
|
CC1-40 |
1 |
10 |
16 | 10 |
M4 |
3.5 |
2 |
10 |
10 | 10 |
M8 |
3.5 |
|
CC1-50 |
1 |
16 |
25 | 25 |
M8 |
3.5 |
2 |
16 |
16 | - |
M8 |
3.5 |
|
CC1-65 |
1 |
16 |
25 | 25 |
M8 |
3.5 |
2 |
16 |
16 | - |
M8 |
3.5 |
|
CC1-80 |
1 |
50 |
50 | 50 |
M8 |
3.5 |
2 |
25 |
35 | - |
M10 |
4.0 |
|
CC1-95 |
1 |
50 |
50 | 50 |
M10 |
4.0 |
2 |
25 |
35 | - |
M10 |
4.0 |
1.L: in main circuit, the distance between terminals and plate;
2.P: in main circuit, the distance between two phases;
3.S: in main circuit, the width of contacting plate.
Model |
A max |
B max |
C max |
D max |
E max |
a |
b |
Φ |
L |
P |
S |
CC1-09(Z)~12(Z) |
47 |
76 |
82(116) |
120.5(154.5) |
140.5(174.5) |
34/35 |
50/60 |
4.5 |
60(95) |
10.5 |
8.6 |
CC1-18(Z) |
47 |
76 |
87(122) |
125.5(160.5) |
145.5(180.5) |
34/35 |
50/60 |
4.5 |
61(96) |
11.3 |
10.4 |
CC1-25(Z) |
57 |
86 |
95(131) |
133.5(169.5) |
153.5(189.5) |
40 |
48 |
4.5 |
70(107) |
13.2 |
11.7 |
CC1-32(Z) |
57 |
86 |
100(138) |
138.5(176.5) |
158.5(196.5) |
40 |
48 |
4.5 |
71.6(120) |
14.5 |
13 |
CC1-4011(Z)~6511(Z) |
77 |
129 |
116(173) |
154.5(211.5) |
174.5(231.5) |
40 |
100/110 |
6.5 |
78(135) |
20 |
8.6 |
CC1-4004/4008(Z)~6504/6508(Z) |
84 |
129 |
116(173) |
154.5(211.5) |
174.5(231.5) |
40 |
100/110 |
6.5 |
78(135) |
20 |
8.6 |
CC1-8011(Z)~9511(Z) |
87 |
129 |
127(188) |
165.5(226.5) |
185.5(246.5) |
40 |
100/110 |
6.5 |
83(140) |
23.5 |
12 |
CC1-8004/8008(Z)~9504/9508(Z) |
96 |
129 |
127(183) |
160.5(221.5) |
180.5(241.5) |
40 |
100/110 |
6.5 |
83(140) |
23.5 |
12 |
Product detail pictures:
Related Product Guide:
"Sincerity, Innovation, Rigorousness, and Efficiency" could be the persistent conception of our organization for your long-term to establish alongside one another with shoppers for mutual reciprocity and mutual benefit for OEM High Quality Medium Voltage Disconnect Switch Supplier – CC1 Series AC Contactor for 9-95A – Changan Group , The product will supply to all over the world, such as: Zambia, Romania, Turkmenistan, We have our own registered brand and our company is developing rapidly owing to high quality products, competitive price and excellent service. We sincerely hope to establish business relations with more friends from home and abroad in the near future. We look forward to your correspondence.
By Octavia from Hyderabad - 2018.09.19 18:37
Timely delivery, strict implementation of the contract provisions of the goods, encountered special circumstances, but also actively cooperate, a trustworthy company!
By Dawn from Zurich - 2018.12.30 10:21