Electric value: AC 50/60Hz, 690V, 0.1A~630A; Tripping class: 10A;
Mounting version:
a.Plug-in: Available for CR2-03,13,23,33,43;
b.Independent: Available for CR2-53, 63; Standard: IEC/EN 60947-4-1
Type Designation
Feature
3.1 3-phase bimetal
3.2Continuously readjustable current settings
3.3Temperature compensation
3.4Tripping indicator
3.5Test button
3.6Stop button
3.7Manual and automatic reset button
Electrically separated 1N/O plus 1N/C contact
Technical Specification
Item |
Series No. |
I/In |
Operating time Tp |
Test condition | |
Overload protection | 1 | 1.05 | >2 h | Start from cold status | |
2 |
1.2 |
≤2h |
Start from heat status, right after item No.1 | ||
3 |
1.5 |
≤2min |
Start from heat status, right after item No.1 | ||
4 | 7.2 | 2s<Tp≤10s | Startfromcoldstatus | ||
Phase failure protection | 5 | Any two phases | Another phase | >2 h | Start from cold status |
1.0 |
0.9 |
||||
6 |
1.15 |
0 |
≤2 h |
Start from heat status, right after item No.5 |
Assembly with contactor
Model of overload relay | Code | Rated current (A) | Recommended fuse type (RT16 is recommended) | Contactor Matched | |
aM |
gG |
||||
CR2-03 |
0301 |
0.1~0.16 |
0.25 |
2 |
CC1-09K CC1-12K |
0302 |
0.16~0.25 |
0.5 |
2 |
||
0303 |
0.25~0.4 |
1 |
2 |
||
0304 |
0.4~0.63 |
1 |
2 |
||
0305 |
0.63~1 |
2 |
4 |
||
0306 |
1~1.6 |
2 |
4 |
||
0307 |
1.6~2.5 |
4 |
6 |
||
0308 |
2.5~4 |
6 |
10 |
||
0310 |
4~6 |
8 |
16 |
||
0312 |
5.5~8 |
12 |
20 |
||
0314 |
7~10 |
12 |
20 |
||
0316 |
9~13 |
16 |
25 |
||
CR2-13 |
1301 |
0.1~0.16 |
0.25 |
2 |
CC1-09 CC1-12 CC1-18 CC1-25 CC1-32 |
1302 |
0.16~0.25 |
0.5 |
2 |
||
1303 |
0.25~0.4 |
1 |
2 |
||
1304 |
0.4~0.63 |
1 |
2 |
||
1305 |
0.63~1 |
2 |
4 |
||
1306 |
1~1.6 |
2 |
4 |
||
1307 |
1.6~2.5 |
4 |
6 |
||
1308 |
2.5~4 |
6 |
10 |
||
1310 |
4~6 |
8 |
16 |
||
1312 |
5.5~8 |
12 |
20 |
||
1314 |
7~10 |
12 |
20 |
||
1316 |
9~13 |
16 |
25 |
||
1321 |
12~18 |
20 |
35 |
||
1322 |
17~25 |
25 |
50 |
||
CR2-23 |
2353 |
23~32 |
40 |
63 |
CC1-32 |
2355 |
30~40 |
40 |
80 |
||
CR2-33 |
3353 |
23~32 |
40 |
63 |
CC1-40 CC1-50 CC1-65 CC1-80 CC1-95 |
3355 |
30~40 |
40 |
100 |
||
3357 |
37~50 |
63 |
100 |
||
3359 |
48~65 |
63 |
100 |
||
3361 |
55~70 |
80 |
125 |
||
3363 |
63~80 |
80 |
125 |
||
3365 |
80~93 |
100 |
160 |
||
CR2-43 |
4366 |
80~104 |
125 |
200 |
CC1-115 CC1-150 |
4367 |
95~120 |
125 |
224 |
||
4368 |
110~150 |
160 |
250 |
||
CR2-53 |
5369 |
80~125 |
125 |
200 |
CC1-115 CC1-185 CC1-150 CC1-225 |
5370 |
100~160 |
160 |
250 |
||
5371 |
125~200 |
200 |
315 |
||
CR2-63 |
6372 |
160~250 |
250 |
400 |
CC1-185 CC1-400 CC1-225 CC1-500 CC1-265 CC1-630 CC1-330 |
6373 |
200~315 |
315 |
500 |
||
6374 |
250~400 |
400 |
630 |
||
6375 |
315~500 |
500 |
800 |
||
6376 |
400~630 |
630 |
800 |
Product detail pictures:
Related Product Guide:
We insist on offering high quality production with good business concept, honest sales and the best and fast service. it will bring you not only the high quality product and huge profit, but the most significant is to occupy the endless market for OEM High Quality Lift Control Box Factory – CR2 Series Thermal Overload Relay – Changan Group , The product will supply to all over the world, such as: Rwanda, Bolivia, Somalia, In order to carry out our goal of "customer first and mutual benefit" in the cooperation, we establish a professional engineering team and a sales team to supply the best service to satisfy our customers' requirements. Welcome you to cooperate with us and join us. We are your best choice.
By Katherine from South Africa - 2018.09.23 18:44
The company leader recept us warmly, through a meticulous and thorough discussion, we signed a purchase order. Hope to cooperate smoothly
By Arabela from Atlanta - 2017.07.28 15:46