Application: remote making & breaking circuits; protect circuit from over-load when assembling with thermal over-load relay; frequent start-up and control of AC contactor;
Electric value: AC50/60Hz, 690V, up to 800A; Utilization category: AC-3, AC-4;
Altitude: ≤2000m;
Ambient temperature: -5℃~+40℃; Mounting category: Ⅲ;
Mounting conditions: inclination between the mounting plane and the vertical plane should not exceed ±5°;
Standard: IEC/EN 60947-4-1
Control Coil Voltage(AC Coil Operation)
Volts(VAC) |
24 |
36 |
42 |
48 |
110 |
127 |
220 |
230 |
240 |
380 |
415 |
440 |
480 |
500 |
600 |
|
Code |
50Hz |
B5 |
C5 |
D5 |
E5 |
F5 |
G5 |
M5 |
P5 |
U5 |
Q5 |
N5 |
R5 |
- |
S5 |
Y5 |
60Hz |
B6 |
- |
D6 |
E6 |
F6 |
G6 |
M6 |
- |
U6 |
Q6 |
- |
R6 |
T6 |
- |
- |
|
50/60Hz |
B7 |
- |
D7 |
E7 |
F7 |
- |
M7 |
P7 |
- |
Q7 |
N7 |
R7 |
- |
- |
- |
Control Coil Voltage(DC Coil Operation)
Volts(VDC) |
12 |
24 |
36 |
48 |
110 |
220 |
Code |
JD |
BD |
CD |
ED |
FD |
MD |
Technical Specification
Standard |
IEC/EN60947-4-1 |
||||||
Model No. |
CC1-115 |
CC1-150 |
CC1-185 |
CC1-225 |
CC1-265 |
CC1-330 |
|
Rated Conventional Heating Current |
Ith (A) |
200 |
200 |
275 |
275 |
315 |
380 |
Rated Voltage Ui(V) |
Ui(V) |
690 |
690 |
690 |
690 |
690 |
690 |
Rated Operation Current Ue=380/415V |
AC-3 Ie(A) |
115 |
150 |
185 |
225 |
265 |
330 |
AC-4 Ie(A) |
52 |
60 |
79 |
86 |
105 |
117 |
|
Power Controlled 3ph cage Motor AC-3 |
380/415V KW |
55 |
75 |
90 |
110 |
132 |
160 |
660/690V KW |
80 |
100 |
110 |
129 |
160 |
220 |
|
Electrial life (x103 operations) |
AC-3 |
600 |
600 |
300 |
300 |
300 |
300 |
AC-4 |
100 |
100 |
100 |
100 |
100 |
100 |
|
Mechanical life (x106 operations) |
6 |
6 |
3 |
3 |
3 |
3 |
|
Matched Fuse |
Size |
RT16-1 |
RT16-2 |
RT16-2 |
RT16-2 |
RT16-2 |
RT16-3 |
A |
200 |
225 |
315 |
315 |
355 |
450 |
|
Main circuit |
3P or 4P |
Standard |
IEC/EN60947-4-1 |
||||||
Model No. |
CC1-400 |
CC1-500 |
CC1-630 |
CC1-780 |
CC1-800 |
CC1-1000 |
|
Rated Conventional Heating Current |
Ith (A) |
460 |
580 |
850 |
1200 |
850 |
1200 |
Rated Voltage Ui(V) |
Ui(V) |
690 |
690 |
690 |
690 |
690 |
690 |
Rated Operation Current Ue=380/415V |
AC-3 Ie(A) |
400 |
500 |
630 |
780 |
800 |
1000 |
AC-4 Ie(A) |
138 |
147 |
188 |
240 |
195 |
320 |
|
Power Controlled 3ph cage Motor AC-3 |
380/415V KW |
200 |
250 |
335 |
400 |
400 |
500 |
660/690V KW |
280 |
335 |
450 |
475 |
475 |
560 |
|
Electrial life (x103 operations) |
AC-3 |
300 |
300 |
300 |
200 |
200 |
200 |
AC-4 |
100 |
100 |
100 |
50 |
50 |
50 |
|
Mechanical life (x106 operations)) |
3 |
3 |
3 |
2 |
3 |
2 |
|
Matched Fuse |
Size |
RT16-3 |
RT16-4 |
RT16-4 |
RT16-4 |
RT16-4 |
RT16-4 |
A |
500 |
630 |
800 |
1250 |
800 |
1250 |
|
Main circuit |
3P or 4P |
4. Terminal CModel | onnection
Cabling(Cu) |
Screw size | Tightening torque (N·m) | ||
Number of piece |
Cable Cross section(mm)2 |
Cu busbar Cross section(mm)2 | |||
CC1-115 |
1 |
70~90 |
- |
M6 |
3 |
CC1-150 |
1 |
70~90 |
- |
M8 |
6 |
CC1-185 |
1 |
95~150 |
- |
M8 |
6 |
CC1-225 |
1 |
95~150 |
- |
M10 |
10 |
CC1-265 |
1 |
120~185 |
- |
M10 |
10 |
CC1-330 |
1 |
185~240 |
- |
M10 |
10 |
CC1-400 |
1(2) |
240(150) |
30×5 |
M10 |
10 |
CC1-500 |
2 |
150~185 |
40×5 |
M10 |
10 |
CC1-630 |
2 |
185~240 |
50×5 |
M12 |
14 |
CC1-800 |
2 |
185~240 |
50×5 |
M12 |
14 |
Model |
A max |
B max |
C max |
CC1-115 |
163.5 |
162 |
171 |
CC1-150 |
163.5 |
170 |
171 |
CC1-185 |
168.5 |
174 |
181 |
CC1-225 |
168.5 |
197 |
181 |
CC1-265 |
201.5 |
203 |
213 |
CC1-330 |
213 |
206 |
219 |
CC1-400 |
213 |
206 |
219 |
CC1-500 |
233 |
238 |
232 |
CC1-630/800 |
309 |
304 |
255 |
Product detail pictures:
![OEM High Quality Insulated Wire Lugs Factories – CC1 AC Contactor for 115-1000A – Changan Group detail pictures](https://cdn.globalso.com/changan-electric/CC1-400.jpg)
![OEM High Quality Insulated Wire Lugs Factories – CC1 AC Contactor for 115-1000A – Changan Group detail pictures](https://cdn.globalso.com/changan-electric/CC1-225.jpg)
![OEM High Quality Insulated Wire Lugs Factories – CC1 AC Contactor for 115-1000A – Changan Group detail pictures](https://cdn.globalso.com/changan-electric/CC1-630.jpg)
![OEM High Quality Insulated Wire Lugs Factories – CC1 AC Contactor for 115-1000A – Changan Group detail pictures](https://cdn.globalso.com/changan-electric/CC1-780.jpg)
Related Product Guide:
Our concentrate on should be to consolidate and enhance the quality and service of present products, meanwhile consistently produce new products to meet unique customers' demands for OEM High Quality Insulated Wire Lugs Factories – CC1 AC Contactor for 115-1000A – Changan Group , The product will supply to all over the world, such as: Ethiopia, Benin, Manila, we are fully determined to control the whole supply chain so as to provide quality products at competitive price in a timely manner. We are keeping up with the advanced techniques, growing through creating more values for our clients and society.
![5 Stars](https://www.changan-electric.com/admin/img/star-icon.png)
Wide range, good quality, reasonable prices and good service, advanced equipment, excellent talents and continuously strengthened technology forces,a nice business partner.
![5 Stars](https://www.changan-electric.com/admin/img/star-icon.png)