Electric value: AC50/60Hz, up to 400V; Standard: IEC/EN 60947-4-1
Ambient temperature:-5℃~+40 ℃,
the average during 24 hours should not exceed +35 ℃; Altitude:≤2000m;
Atmosphere conditions: At mounting site,
relative humidity not exceed 50% at the max temperature of +40℃, higher relative humidity is allowable
under lower temperature. For example, RH could be 90% at +20℃,
special measures should be taken to occurrence of dews; Pollution degree: 3
Installation category: Ⅲ
Installation conditions :
the inclination between installation plane and vertical plane is within ± 5 °
Impact and shake: the products should locate
in the places where there are no obvious impact and shake.
Technical Specification
Standard |
IEC/EN60947-4-1 |
||||||
Model No. |
CJ19-25 |
CJ19-32 |
CJ19-43 |
CJ19-63 |
CJ19-80 |
CJ19-95 |
|
Rated Conventional Heating Current |
Ith (A) |
25 |
32 |
43 |
63 |
80 |
95 |
Rated Work Current |
415V/Ie (A) |
18 |
25 |
32 |
60 |
80 |
95 |
Capacitor Controlled |
220V/240V(Kvar) |
6 |
9 |
10 |
15 |
18 |
22 |
400V/440V(Kvar) |
12 |
18 |
20 |
30 |
36 |
40 |
|
Rated Insulation Voltage |
Ui(V) |
690 |
690 |
690 |
690 |
690 |
690 |
Rated Operation Voltage Electrial life(x103 ) |
Ue(V) |
400 |
400 |
400 |
400 |
400 |
400 |
Times |
120 |
120 |
120 |
100 |
100 |
100 |
|
Mechanical life(x103 ) |
Times |
3000 |
3000 |
3000 |
3000 |
3000 |
3000 |
Restrained Surge Capacity |
x Ie |
15 |
|||||
Auxiliary Contact |
Ith=10A |
AC-15 360VA;DC-13 33W |
|||||
Control Capacity |
COIL PARAMETERS
Coil Power(VA) |
Start-up |
76 |
110 |
110 |
230 |
230 |
230 |
Holding |
10 |
11 |
11 |
32 |
32 |
32 |
|
Rated Control Power |
Us(V) |
24,36,48,110,220,380 |
|||||
Pull time |
Ms |
12~22 |
15~24 |
15~24 |
20~26 |
20~35 |
20~35 |
Release time |
Ms |
4~12 |
5~19 |
5~19 |
8~12 |
6~20 |
6~20 |
Operation Range |
Pick-up |
(85%-110%)Us |
|||||
Drop-out |
(20%-75%)Us |
Model |
Amax |
Bmax |
Cmax |
Dmax |
E |
F |
Note |
CJ19-25 |
80 |
47 |
124 |
76 |
34/35 |
50/60 |
be fixed with 35mm din rail |
CJ19-32 |
90 |
58 |
132 |
86 |
40 |
48 |
|
CJ19-43 |
90 |
58 |
136 |
86 |
40 |
48 |
|
CJ19-63 |
132 |
79 |
150 |
- |
- |
- |
Not only fixed by screws but also couldbe fixed with 35mm and 75mm din rail |
CJ19-80~95 |
135 |
87 |
158 |
- |
- |
- |
Wiring and installation
5.1The connection terminals are protected through insulation cover, which is reliable and secure for installation and operation;
5.2For CJ19-25~43, screws are available for installation, as well as the DIN rail; for CJ19-63~95, 35mm or 75mm standard rail are available for installation.
Product detail pictures:
Related Product Guide:
Our business aims to operating faithfully, serving to all of our clients , and working in new technology and new machine continuously for ODM Solar Panel Surge Protector Factories – CJ19 Series Capacitor Switching Contactor – Changan Group , The product will supply to all over the world, such as: Chile, Algeria, Thailand, We hope we can establish long-term cooperation with all of the customers, and hope we can improve competitiveness and achieve the win-win situation together with the customers. We sincerely welcome the customers from all over the world to contact us for anything you need to have!Welcome all customers both at home and abroad to visit our factory. We hope to have win-win business relationships with you, and create a better tomorrow.