ODM Metal Clad Fuse Factory – CC1 AC Contactor for 9-95A – Changan Group
ODM Metal Clad Fuse Factory – CC1 AC Contactor for 9-95A – Changan Group Detail:
Description
Application: remote making & breaking circuits; protect circuit from over-load when assembling with thermal over-load relay; frequent start-up and control of AC contactor;
Electric value: AC50/60Hz, 690V, up to 95A; Utilization category: AC-3, AC-4;
Altitude: ≤2000m;
Ambient temperature: -5℃~+40℃; Mounting category: Ⅲ;
Mounting conditions: inclination between the mounting plane and the vertical plane should not exceed ±5°;
Standard: IEC/EN 60947-4-1. IEC/EN 60947-5-1.
Control Coil Voltage(AC Coil Operation)
Volts(VAC) |
24 |
36 |
42 |
48 |
110 |
127 |
220 |
230 |
240 |
380 |
415 |
440 |
480 |
500 |
600 |
|
Code |
50Hz |
B5 |
C5 |
D5 |
E5 |
F5 |
G5 |
M5 |
P5 |
U5 |
Q5 |
N5 |
R5 |
- |
S5 |
Y5 |
60Hz |
B6 |
- |
D6 |
E6 |
F6 |
G6 |
M6 |
- |
U6 |
Q6 |
- |
R6 |
T6 |
- |
- |
|
50/60Hz |
B7 |
- |
D7 |
E7 |
F7 |
- |
M7 |
P7 |
- |
Q7 |
N7 |
R7 |
- |
- |
- |
Control Coil Voltage(DC Coil Operation)
Volts(VDC) |
12 |
24 |
36 |
48 |
110 |
220 |
Code |
JD |
BD |
CD |
ED |
FD |
MD |
Technical Specification
Standard | IEC/EN60947-4-1 IEC/EN60947-5-1 | |||||
Model No. |
CC1-09 |
CC1-12 |
CC1-18 |
CC1-25 |
CC1-32 |
|
Rated Conventional Heating Current |
Ith (A) |
20 |
20 |
32 |
40 |
50 |
Rated Voltage Ui(V) |
Ui(V) |
690 |
690 |
690 |
690 |
690 |
Rated Operation CurrentUe=380/415V |
AC-3 Ie(A) |
9 |
12 |
18 |
25 |
32 |
AC-4 Ie(A) |
3.5 |
5 |
7.7 |
8.5 |
12 |
|
Power Controlled 3ph cage MotorAC-3 |
220/240V KW |
2.2 |
3 |
4 |
5.5 |
7.5 |
380/415V KW |
4 |
5.5 |
7.5 |
11 |
15 |
|
660/690V KW |
5.5 |
7.5 |
10 |
15 |
18.5 |
|
Electrial life(x103 operations) |
AC-3 |
1000 |
1000 |
1000 |
1000 |
800 |
AC-4 |
200 |
200 |
200 |
200 |
200 |
|
Mechanical life(x106 operations) |
10 |
10 |
10 |
10 |
8 |
|
Matched Fuse |
Size |
RT16-00 |
RT16-00 |
RT16-00 |
RT16-00 |
RT16-00 |
A |
20 |
20 |
32 |
40 |
50 |
|
Main circuit |
3P or 4P |
|||||
Auxiliary circuit Cat.:AC-15,Ue=415V Ie=0.95A Ith=10A | 1NO or 1NC |
Standard | IEC/EN60947-4-1 IEC/EN60947-5-1 | |||||
Model No. |
CC1-40 |
CC1-50 |
CC1-65 |
CC1-80 |
CC1-95 |
|
Rated Conventional Heating Current |
Ith (A) |
60 |
80 |
80 |
100 |
125 |
Rated Voltage Ui(V) |
Ui(V) |
690 |
690 |
690 |
690 |
690 |
Rated Operation CurrentUe=380/415V |
AC-3 Ie(A) |
40 |
50 |
65 |
80 |
95 |
AC-4 Ie(A) |
18.5 |
24 |
28 |
37 |
44 |
|
Power Controlled 3ph cage MotorAC-3 |
220/240V KW |
11 |
15 |
18.5 |
22 |
25 |
380/415V KW |
18.5 |
22 |
30 |
37 |
45 |
|
660/690V KW |
30 |
33 |
37 |
45 |
45 |
|
Electrial life(x103 operations) |
AC-3 |
800 |
600 |
600 |
600 |
600 |
AC-4 |
150 |
150 |
150 |
100 |
100 |
|
Mechanical life(x106 operations) |
8 |
8 |
8 |
6 |
6 |
|
Matched Fuse |
Size |
RT16-00 |
RT16-00 |
RT16-00 |
RT16-00 |
RT16-00 |
A |
63 |
80 |
80 |
100 |
125 |
|
Main circuit |
3P or 4P |
|||||
Auxiliary circuit Cat.:AC-15,Ue=415V Ie=0.95A Ith=10A |
1NO+1NC |
Model |
Cabling cross section(Cu) |
screw size | Tightening torque(N.m) | |||
Number of piece |
Flexible cable with cold-pressed socket(mm2 ) |
Flexible cable without cold- pressed socket(mm2 ) |
Inflexible cable(mm2 ) | |||
CC1-09 |
1~2 |
2.5 |
4 | 4 |
M3.5 |
0.8 |
CC1-12 |
1~2 |
2.5 |
4 | 4 |
M3.5 |
0.8 |
CC1-18 |
1~2 |
4 |
6 | 6 |
M3.5 |
0.8 |
CC1-25 |
1 |
4 |
10 | 6 |
M4 |
1.2 |
2 |
4 |
6 | 6 |
M4 |
1.2 |
|
CC1-32 |
1 |
4 |
10 | 6 |
M4 |
1.2 |
2 |
4 |
6 | 6 |
M4 |
1.2 |
|
CC1-40 |
1 |
10 |
16 | 10 |
M4 |
3.5 |
2 |
10 |
10 | 10 |
M8 |
3.5 |
|
CC1-50 |
1 |
16 |
25 | 25 |
M8 |
3.5 |
2 |
16 |
16 | - |
M8 |
3.5 |
|
CC1-65 |
1 |
16 |
25 | 25 |
M8 |
3.5 |
2 |
16 |
16 | - |
M8 |
3.5 |
|
CC1-80 |
1 |
50 |
50 | 50 |
M8 |
3.5 |
2 |
25 |
35 | - |
M10 |
4.0 |
|
CC1-95 |
1 |
50 |
50 | 50 |
M10 |
4.0 |
2 |
25 |
35 | - |
M10 |
4.0 |
1.L: in main circuit, the distance between terminals and plate;
2.P: in main circuit, the distance between two phases;
3.S: in main circuit, the width of contacting plate.
Model |
A max |
B max |
C max |
D max |
E max |
a |
b |
Φ |
L |
P |
S |
CC1-09(Z)~12(Z) |
47 |
76 |
82(116) |
120.5(154.5) |
140.5(174.5) |
34/35 |
50/60 |
4.5 |
60(95) |
10.5 |
8.6 |
CC1-18(Z) |
47 |
76 |
87(122) |
125.5(160.5) |
145.5(180.5) |
34/35 |
50/60 |
4.5 |
61(96) |
11.3 |
10.4 |
CC1-25(Z) |
57 |
86 |
95(131) |
133.5(169.5) |
153.5(189.5) |
40 |
48 |
4.5 |
70(107) |
13.2 |
11.7 |
CC1-32(Z) |
57 |
86 |
100(138) |
138.5(176.5) |
158.5(196.5) |
40 |
48 |
4.5 |
71.6(120) |
14.5 |
13 |
CC1-4011(Z)~6511(Z) |
77 |
129 |
116(173) |
154.5(211.5) |
174.5(231.5) |
40 |
100/110 |
6.5 |
78(135) |
20 |
8.6 |
CC1-4004/4008(Z)~6504/6508(Z) |
84 |
129 |
116(173) |
154.5(211.5) |
174.5(231.5) |
40 |
100/110 |
6.5 |
78(135) |
20 |
8.6 |
CC1-8011(Z)~9511(Z) |
87 |
129 |
127(188) |
165.5(226.5) |
185.5(246.5) |
40 |
100/110 |
6.5 |
83(140) |
23.5 |
12 |
CC1-8004/8008(Z)~9504/9508(Z) |
96 |
129 |
127(183) |
160.5(221.5) |
180.5(241.5) |
40 |
100/110 |
6.5 |
83(140) |
23.5 |
12 |
Product detail pictures:
Related Product Guide:
We've got a specialist, effectiveness staff to supply high quality service for our shopper. We always follow the tenet of customer-oriented, details-focused for ODM Metal Clad Fuse Factory – CC1 AC Contactor for 9-95A – Changan Group , The product will supply to all over the world, such as: Los Angeles, Nicaragua, Kenya, We have 48 provincial agencies in the country. We also have stable cooperation with several international trading companies. They place order with us and export products to other countries. We expect to cooperate with you to develop a larger market.
By Lindsay from Mexico - 2018.12.14 15:26
The sales manager has a good English level and skilled professional knowledge, we have a good communication. He is a warm and cheerful man, we have a pleasant cooperation and we became very good friends in private.
By Victor Yanushkevich from Panama - 2017.03.28 16:34