ODM Insulated Wire Lugs Supplier – CS2 Series Motor Protection Circuit Breaker – Changan Group
ODM Insulated Wire Lugs Supplier – CS2 Series Motor Protection Circuit Breaker – Changan Group Detail:
Description
Electric value: AC690V, 32A, 80A;
Standard: IEC/EN 60947-2, IEC60947-4-1
Type Designation
Operating Condition
3.1 Temperature: -5 ℃~+40℃ ,average temperature in 24 hours not exceed +35 ℃
3.2 Altitude: not exceed 2000m
3.3 Air conditions:
At mounting site, relative humidity not exceed 50% at the max temperature of +40℃, higher
relative humidity is allowable under lower temperature,for example, RH could be 90% at +20℃
3.4 Pollution grade: Grade Ⅲ
3.5 Release grade: 10A(CS2-32) 10A(CS2-80)
3.6 Rated operational system: Continuous operational system
3.7 Mounting conditions:
The inclination between the mounting plane and the vertical plane shall not exceed 5 ° The product shall be installed and operated at a place without obvious shake, Impact and vibration.
Technical Specification
4.1 Protection property
Series No. | Multiple of setting current | Initial status | Time | Expected results | Ambient temperature | |
1 | 1.05 | Cold status | t≥2h | Non-tripping | +20℃±2℃ | |
2 | 1.20 | Heat status (right after test.1) | t<2h | Tripping | +20℃±2℃ | |
3 | 1.50 | Heat status (right after test.1) | Tripping class | 10A t<2min | Tripping | +20℃±2℃ |
10 t<4min | ||||||
4 | 7.20 | Cold status | Tripping class | 10A 2s<t≤10s | Tripping | +20℃±2℃ |
Phase failure protection properties
Series No. |
Multiple of setting current |
Initial status |
Time |
Expected results | Ambient temperature | |
Any 2 phase | The other phase | |||||
1 | 1.0 | 0.9 | Cold status |
t≥2h |
Non-tripping | +20℃±2℃ |
2 | 1.15 | 0 | Heat status
(right after test.1) |
t <2h |
Tripping | +20℃±2℃ |
Temperature compensation properties
Series No. | Multiple of setting current | Initial status | Time | Expected results | Ambient temperature |
1 | 1.0 | Cold status | t≥2h | Non-tripping |
+40℃±2℃ |
2 | 1.2 | Heat status (right after test.1) | t<2h | Tripping | +40℃±2℃ |
3 | 1.05 | Cold status | t≥2h | Non-tripping |
-5℃±2℃ |
4 | 1.3 | Heat status (right after test.3) | t<2h | Tripping | -5℃±2℃ |
Model of overload relay | Code | Rated current (A) | Rated ultimate short-circuit breaking capacity Icu(kA) | Rated service short-circuit breaking capacity Ics(kA) | Standard rated power of three-phase motor (kW) | ||||||
230/240V | 400/415V | 660/690V | 230/240V | 400/415V | 660/690V | 230/240V | 400/415V | 660/690V | |||
CS2-32 |
3201 |
0.1~0.16 | 100 | 100 | 100 | 100 | 100 | 100 | - | - | - |
3202 |
0.16~0.25 | 100 | 100 | 100 | 100 | 100 | 100 | - | - | - | |
3203 |
0.25~0.4 | 100 | 100 | 100 | 100 | 100 | 100 | - | - | - | |
3204 |
0.4~0.63 | 100 | 100 | 100 | 100 | 100 | 100 | - | - | 0.37 | |
3205 |
0.63~1 | 100 | 100 | 100 | 100 | 100 | 100 | - | - | 0.55 | |
3206 |
1~1.6 | 100 | 100 | 100 | 100 | 100 | 100 | - | - | 1.1 | |
3207 |
1.6~2.5 | 100 | 100 | 3 | 100 | 100 | 2.25 | 0.37 | 0.75 | 1.5 | |
3208 |
2.5~4 | 100 | 100 | 3 | 100 | 100 | 2.25 | 0.75 | 1.5 | 3 | |
3210 |
4~6.3 | 100 | 100 | 3 | 100 | 100 | 2.25 | 1.1 | 2.2 | 4 | |
3214 |
6~10 | 100 | 100 | 3 | 100 | 100 | 2.25 | 2.2 | 4 | 7.5 | |
3216 |
9~14 | 100 | 15 | 3 | 100 | 7.5 | 2.25 | 3 | 5.5 | 9 | |
3220 |
13~18 | 100 | 15 | 3 | 100 | 7.5 | 2.25 | 4 | 9 | 11 | |
3221 |
17~23 | 50 | 15 | 3 | 50 | 6 | 2.25 | 5.5 | 11 | 15 | |
3222 |
20~25 | 50 | 15 | 3 | 50 | 6 | 2.25 | 5.5 | 11 | 18.5 | |
3232 |
24~32 | 50 | 15 | 3 | 50 | 6 | 2.25 | 7.5 | 12.5 | 22 | |
CS2-80 |
8025 |
16~25 | - | 15 | - | - | 7.5 | - | 5.5 | 11 | - |
8040 |
25~40 | - | 15 | - | - | 7.5 | - | 11 | 22 | - | |
8063 |
40~63 | - | 15 | - | - | 7.5 | - | 15 | 33 | - | |
8080 |
56~80 | - | 15 | - | - | 7.5 | - | 22 | 45 | - |
Product detail pictures:
Related Product Guide:
"Sincerity, Innovation, Rigorousness, and Efficiency" would be the persistent conception of our corporation to the long-term to establish collectively with customers for mutual reciprocity and mutual benefit for ODM Insulated Wire Lugs Supplier – CS2 Series Motor Protection Circuit Breaker – Changan Group , The product will supply to all over the world, such as: Nepal, Panama, Chile, Customer satisfaction is our first goal. Our mission is to pursue the superlative quality, making continual progress. We sincerely welcome you to make progress hand in hand with us, and construct a prosperous future together.