ODM Dual Indicator Light Suppliers – CS2 Series Motor Protection Circuit Breaker – Changan Group
ODM Dual Indicator Light Suppliers – CS2 Series Motor Protection Circuit Breaker – Changan Group Detail:
Description
Electric value: AC690V, 32A, 80A;
Standard: IEC/EN 60947-2, IEC60947-4-1
Type Designation
Operating Condition
3.1 Temperature: -5 ℃~+40℃ ,average temperature in 24 hours not exceed +35 ℃
3.2 Altitude: not exceed 2000m
3.3 Air conditions:
At mounting site, relative humidity not exceed 50% at the max temperature of +40℃, higher
relative humidity is allowable under lower temperature,for example, RH could be 90% at +20℃
3.4 Pollution grade: Grade Ⅲ
3.5 Release grade: 10A(CS2-32) 10A(CS2-80)
3.6 Rated operational system: Continuous operational system
3.7 Mounting conditions:
The inclination between the mounting plane and the vertical plane shall not exceed 5 ° The product shall be installed and operated at a place without obvious shake, Impact and vibration.
Technical Specification
4.1 Protection property
Series No. | Multiple of setting current | Initial status | Time | Expected results | Ambient temperature | |
1 | 1.05 | Cold status | t≥2h | Non-tripping | +20℃±2℃ | |
2 | 1.20 | Heat status (right after test.1) | t<2h | Tripping | +20℃±2℃ | |
3 | 1.50 | Heat status (right after test.1) | Tripping class | 10A t<2min | Tripping | +20℃±2℃ |
10 t<4min | ||||||
4 | 7.20 | Cold status | Tripping class | 10A 2s<t≤10s | Tripping | +20℃±2℃ |
Phase failure protection properties
Series No. |
Multiple of setting current |
Initial status |
Time |
Expected results | Ambient temperature | |
Any 2 phase | The other phase | |||||
1 | 1.0 | 0.9 | Cold status |
t≥2h |
Non-tripping | +20℃±2℃ |
2 | 1.15 | 0 | Heat status
(right after test.1) |
t <2h |
Tripping | +20℃±2℃ |
Temperature compensation properties
Series No. | Multiple of setting current | Initial status | Time | Expected results | Ambient temperature |
1 | 1.0 | Cold status | t≥2h | Non-tripping |
+40℃±2℃ |
2 | 1.2 | Heat status (right after test.1) | t<2h | Tripping | +40℃±2℃ |
3 | 1.05 | Cold status | t≥2h | Non-tripping |
-5℃±2℃ |
4 | 1.3 | Heat status (right after test.3) | t<2h | Tripping | -5℃±2℃ |
Model of overload relay | Code | Rated current (A) | Rated ultimate short-circuit breaking capacity Icu(kA) | Rated service short-circuit breaking capacity Ics(kA) | Standard rated power of three-phase motor (kW) | ||||||
230/240V | 400/415V | 660/690V | 230/240V | 400/415V | 660/690V | 230/240V | 400/415V | 660/690V | |||
CS2-32 |
3201 |
0.1~0.16 | 100 | 100 | 100 | 100 | 100 | 100 | - | - | - |
3202 |
0.16~0.25 | 100 | 100 | 100 | 100 | 100 | 100 | - | - | - | |
3203 |
0.25~0.4 | 100 | 100 | 100 | 100 | 100 | 100 | - | - | - | |
3204 |
0.4~0.63 | 100 | 100 | 100 | 100 | 100 | 100 | - | - | 0.37 | |
3205 |
0.63~1 | 100 | 100 | 100 | 100 | 100 | 100 | - | - | 0.55 | |
3206 |
1~1.6 | 100 | 100 | 100 | 100 | 100 | 100 | - | - | 1.1 | |
3207 |
1.6~2.5 | 100 | 100 | 3 | 100 | 100 | 2.25 | 0.37 | 0.75 | 1.5 | |
3208 |
2.5~4 | 100 | 100 | 3 | 100 | 100 | 2.25 | 0.75 | 1.5 | 3 | |
3210 |
4~6.3 | 100 | 100 | 3 | 100 | 100 | 2.25 | 1.1 | 2.2 | 4 | |
3214 |
6~10 | 100 | 100 | 3 | 100 | 100 | 2.25 | 2.2 | 4 | 7.5 | |
3216 |
9~14 | 100 | 15 | 3 | 100 | 7.5 | 2.25 | 3 | 5.5 | 9 | |
3220 |
13~18 | 100 | 15 | 3 | 100 | 7.5 | 2.25 | 4 | 9 | 11 | |
3221 |
17~23 | 50 | 15 | 3 | 50 | 6 | 2.25 | 5.5 | 11 | 15 | |
3222 |
20~25 | 50 | 15 | 3 | 50 | 6 | 2.25 | 5.5 | 11 | 18.5 | |
3232 |
24~32 | 50 | 15 | 3 | 50 | 6 | 2.25 | 7.5 | 12.5 | 22 | |
CS2-80 |
8025 |
16~25 | - | 15 | - | - | 7.5 | - | 5.5 | 11 | - |
8040 |
25~40 | - | 15 | - | - | 7.5 | - | 11 | 22 | - | |
8063 |
40~63 | - | 15 | - | - | 7.5 | - | 15 | 33 | - | |
8080 |
56~80 | - | 15 | - | - | 7.5 | - | 22 | 45 | - |
Product detail pictures:
Related Product Guide:
We insist on offering high quality production with good business concept, honest sales and the best and fast service. it will bring you not only the high quality product and huge profit, but the most significant is to occupy the endless market for ODM Dual Indicator Light Suppliers – CS2 Series Motor Protection Circuit Breaker – Changan Group , The product will supply to all over the world, such as: Egypt, Bolivia, Curacao, Ensuring high product quality by choosing the best suppliers, we have also implemented comprehensive quality control processes throughout our sourcing procedures. Meanwhile, our access to a large range of factories, coupled with our excellent management, also ensures that we can quickly fill your requirements at the best prices, regardless the order size.