ODM Contactor Factories – CC1 AC Contactor for 9-95A – Changan Group
ODM Contactor Factories – CC1 AC Contactor for 9-95A – Changan Group Detail:
Description
Application: remote making & breaking circuits; protect circuit from over-load when assembling with thermal over-load relay; frequent start-up and control of AC contactor;
Electric value: AC50/60Hz, 690V, up to 95A; Utilization category: AC-3, AC-4;
Altitude: ≤2000m;
Ambient temperature: -5℃~+40℃; Mounting category: Ⅲ;
Mounting conditions: inclination between the mounting plane and the vertical plane should not exceed ±5°;
Standard: IEC/EN 60947-4-1. IEC/EN 60947-5-1.
Control Coil Voltage(AC Coil Operation)
Volts(VAC) |
24 |
36 |
42 |
48 |
110 |
127 |
220 |
230 |
240 |
380 |
415 |
440 |
480 |
500 |
600 |
|
Code |
50Hz |
B5 |
C5 |
D5 |
E5 |
F5 |
G5 |
M5 |
P5 |
U5 |
Q5 |
N5 |
R5 |
- |
S5 |
Y5 |
60Hz |
B6 |
- |
D6 |
E6 |
F6 |
G6 |
M6 |
- |
U6 |
Q6 |
- |
R6 |
T6 |
- |
- |
|
50/60Hz |
B7 |
- |
D7 |
E7 |
F7 |
- |
M7 |
P7 |
- |
Q7 |
N7 |
R7 |
- |
- |
- |
Control Coil Voltage(DC Coil Operation)
Volts(VDC) |
12 |
24 |
36 |
48 |
110 |
220 |
Code |
JD |
BD |
CD |
ED |
FD |
MD |
Technical Specification
Standard | IEC/EN60947-4-1 IEC/EN60947-5-1 | |||||
Model No. |
CC1-09 |
CC1-12 |
CC1-18 |
CC1-25 |
CC1-32 |
|
Rated Conventional Heating Current |
Ith (A) |
20 |
20 |
32 |
40 |
50 |
Rated Voltage Ui(V) |
Ui(V) |
690 |
690 |
690 |
690 |
690 |
Rated Operation CurrentUe=380/415V |
AC-3 Ie(A) |
9 |
12 |
18 |
25 |
32 |
AC-4 Ie(A) |
3.5 |
5 |
7.7 |
8.5 |
12 |
|
Power Controlled 3ph cage MotorAC-3 |
220/240V KW |
2.2 |
3 |
4 |
5.5 |
7.5 |
380/415V KW |
4 |
5.5 |
7.5 |
11 |
15 |
|
660/690V KW |
5.5 |
7.5 |
10 |
15 |
18.5 |
|
Electrial life(x103 operations) |
AC-3 |
1000 |
1000 |
1000 |
1000 |
800 |
AC-4 |
200 |
200 |
200 |
200 |
200 |
|
Mechanical life(x106 operations) |
10 |
10 |
10 |
10 |
8 |
|
Matched Fuse |
Size |
RT16-00 |
RT16-00 |
RT16-00 |
RT16-00 |
RT16-00 |
A |
20 |
20 |
32 |
40 |
50 |
|
Main circuit |
3P or 4P |
|||||
Auxiliary circuit Cat.:AC-15,Ue=415V Ie=0.95A Ith=10A | 1NO or 1NC |
Standard | IEC/EN60947-4-1 IEC/EN60947-5-1 | |||||
Model No. |
CC1-40 |
CC1-50 |
CC1-65 |
CC1-80 |
CC1-95 |
|
Rated Conventional Heating Current |
Ith (A) |
60 |
80 |
80 |
100 |
125 |
Rated Voltage Ui(V) |
Ui(V) |
690 |
690 |
690 |
690 |
690 |
Rated Operation CurrentUe=380/415V |
AC-3 Ie(A) |
40 |
50 |
65 |
80 |
95 |
AC-4 Ie(A) |
18.5 |
24 |
28 |
37 |
44 |
|
Power Controlled 3ph cage MotorAC-3 |
220/240V KW |
11 |
15 |
18.5 |
22 |
25 |
380/415V KW |
18.5 |
22 |
30 |
37 |
45 |
|
660/690V KW |
30 |
33 |
37 |
45 |
45 |
|
Electrial life(x103 operations) |
AC-3 |
800 |
600 |
600 |
600 |
600 |
AC-4 |
150 |
150 |
150 |
100 |
100 |
|
Mechanical life(x106 operations) |
8 |
8 |
8 |
6 |
6 |
|
Matched Fuse |
Size |
RT16-00 |
RT16-00 |
RT16-00 |
RT16-00 |
RT16-00 |
A |
63 |
80 |
80 |
100 |
125 |
|
Main circuit |
3P or 4P |
|||||
Auxiliary circuit Cat.:AC-15,Ue=415V Ie=0.95A Ith=10A |
1NO+1NC |
Model |
Cabling cross section(Cu) |
screw size | Tightening torque(N.m) | |||
Number of piece |
Flexible cable with cold-pressed socket(mm2 ) |
Flexible cable without cold- pressed socket(mm2 ) |
Inflexible cable(mm2 ) | |||
CC1-09 |
1~2 |
2.5 |
4 | 4 |
M3.5 |
0.8 |
CC1-12 |
1~2 |
2.5 |
4 | 4 |
M3.5 |
0.8 |
CC1-18 |
1~2 |
4 |
6 | 6 |
M3.5 |
0.8 |
CC1-25 |
1 |
4 |
10 | 6 |
M4 |
1.2 |
2 |
4 |
6 | 6 |
M4 |
1.2 |
|
CC1-32 |
1 |
4 |
10 | 6 |
M4 |
1.2 |
2 |
4 |
6 | 6 |
M4 |
1.2 |
|
CC1-40 |
1 |
10 |
16 | 10 |
M4 |
3.5 |
2 |
10 |
10 | 10 |
M8 |
3.5 |
|
CC1-50 |
1 |
16 |
25 | 25 |
M8 |
3.5 |
2 |
16 |
16 | - |
M8 |
3.5 |
|
CC1-65 |
1 |
16 |
25 | 25 |
M8 |
3.5 |
2 |
16 |
16 | - |
M8 |
3.5 |
|
CC1-80 |
1 |
50 |
50 | 50 |
M8 |
3.5 |
2 |
25 |
35 | - |
M10 |
4.0 |
|
CC1-95 |
1 |
50 |
50 | 50 |
M10 |
4.0 |
2 |
25 |
35 | - |
M10 |
4.0 |
1.L: in main circuit, the distance between terminals and plate;
2.P: in main circuit, the distance between two phases;
3.S: in main circuit, the width of contacting plate.
Model |
A max |
B max |
C max |
D max |
E max |
a |
b |
Φ |
L |
P |
S |
CC1-09(Z)~12(Z) |
47 |
76 |
82(116) |
120.5(154.5) |
140.5(174.5) |
34/35 |
50/60 |
4.5 |
60(95) |
10.5 |
8.6 |
CC1-18(Z) |
47 |
76 |
87(122) |
125.5(160.5) |
145.5(180.5) |
34/35 |
50/60 |
4.5 |
61(96) |
11.3 |
10.4 |
CC1-25(Z) |
57 |
86 |
95(131) |
133.5(169.5) |
153.5(189.5) |
40 |
48 |
4.5 |
70(107) |
13.2 |
11.7 |
CC1-32(Z) |
57 |
86 |
100(138) |
138.5(176.5) |
158.5(196.5) |
40 |
48 |
4.5 |
71.6(120) |
14.5 |
13 |
CC1-4011(Z)~6511(Z) |
77 |
129 |
116(173) |
154.5(211.5) |
174.5(231.5) |
40 |
100/110 |
6.5 |
78(135) |
20 |
8.6 |
CC1-4004/4008(Z)~6504/6508(Z) |
84 |
129 |
116(173) |
154.5(211.5) |
174.5(231.5) |
40 |
100/110 |
6.5 |
78(135) |
20 |
8.6 |
CC1-8011(Z)~9511(Z) |
87 |
129 |
127(188) |
165.5(226.5) |
185.5(246.5) |
40 |
100/110 |
6.5 |
83(140) |
23.5 |
12 |
CC1-8004/8008(Z)~9504/9508(Z) |
96 |
129 |
127(183) |
160.5(221.5) |
180.5(241.5) |
40 |
100/110 |
6.5 |
83(140) |
23.5 |
12 |
Product detail pictures:
Related Product Guide:
The organization keeps on the procedure concept "scientific management, high quality and efficiency primacy, purchaser supreme for ODM Contactor Factories – CC1 AC Contactor for 9-95A – Changan Group , The product will supply to all over the world, such as: Nepal, India, Munich, With the best technological support, we have tailored our website for the best user experience and kept in mind your ease of shopping. we ensure that the best reaches you at your doorstep, in the shortest possible time and with the help of our efficient logistical partners i.e DHL and UPS. We promise quality, living by the motto of promising only what we can deliver.
By Rosemary from Singapore - 2017.10.23 10:29
We always believe that the details decides the company's product quality, in this respect, the company conform our requirements and the goods are meet our expectations.
By Marcie Green from Cambodia - 2018.09.29 17:23