Description
Electric value: AC50/60Hz, up to 400V; Standard: IEC/EN 60947-4-1
Ambient temperature:-5℃~+40 ℃,
the average during 24 hours should not exceed +35 ℃; Altitude:≤2000m;
Atmosphere conditions: At mounting site,
relative humidity not exceed 50% at the max temperature of +40℃, higher relative humidity is allowable
under lower temperature. For example, RH could be 90% at +20℃,
special measures should be taken to occurrence of dews; Pollution degree: 3
Installation category: Ⅲ
Installation conditions :
the inclination between installation plane and vertical plane is within ± 5 °
Impact and shake: the products should locate
in the places where there are no obvious impact and shake.
Technical Specification
Standard |
IEC/EN60947-4-1 |
||||||
Model No. |
CJ19-25 |
CJ19-32 |
CJ19-43 |
CJ19-63 |
CJ19-80 |
CJ19-95 |
|
Rated Conventional Heating Current |
Ith (A) |
25 |
32 |
43 |
63 |
80 |
95 |
Rated Work Current |
415V/Ie (A) |
18 |
25 |
32 |
60 |
80 |
95 |
Capacitor Controlled |
220V/240V(Kvar) |
6 |
9 |
10 |
15 |
18 |
22 |
400V/440V(Kvar) |
12 |
18 |
20 |
30 |
36 |
40 |
|
Rated Insulation Voltage |
Ui(V) |
690 |
690 |
690 |
690 |
690 |
690 |
Rated Operation Voltage Electrial life(x103 ) |
Ue(V) |
400 |
400 |
400 |
400 |
400 |
400 |
Times |
120 |
120 |
120 |
100 |
100 |
100 |
|
Mechanical life(x103 ) |
Times |
3000 |
3000 |
3000 |
3000 |
3000 |
3000 |
Restrained Surge Capacity |
x Ie |
15 |
|||||
Auxiliary Contact |
Ith=10A |
AC-15 360VA;DC-13 33W |
|||||
Control Capacity |
COIL PARAMETERS
Coil Power(VA) |
Start-up |
76 |
110 |
110 |
230 |
230 |
230 |
Holding |
10 |
11 |
11 |
32 |
32 |
32 |
|
Rated Control Power |
Us(V) |
24,36,48,110,220,380 |
|||||
Pull time |
Ms |
12~22 |
15~24 |
15~24 |
20~26 |
20~35 |
20~35 |
Release time |
Ms |
4~12 |
5~19 |
5~19 |
8~12 |
6~20 |
6~20 |
Operation Range |
Pick-up |
(85%-110%)Us |
|||||
Drop-out |
(20%-75%)Us |
Model |
Amax |
Bmax |
Cmax |
Dmax |
E |
F |
Note |
CJ19-25 |
80 |
47 |
124 |
76 |
34/35 |
50/60 |
be fixed with 35mm din rail |
CJ19-32 |
90 |
58 |
132 |
86 |
40 |
48 |
|
CJ19-43 |
90 |
58 |
136 |
86 |
40 |
48 |
|
CJ19-63 |
132 |
79 |
150 |
- |
- |
- |
Not only fixed by screws but also couldbe fixed with 35mm and 75mm din rail |
CJ19-80~95 |
135 |
87 |
158 |
- |
- |
- |
Wiring and installation
5.1The connection terminals are protected through insulation cover, which is reliable and secure for installation and operation;
5.2For CJ19-25~43, screws are available for installation, as well as the DIN rail; for CJ19-63~95, 35mm or 75mm standard rail are available for installation.
Product detail pictures:
Related Product Guide:
We aim to find out quality disfigurement from the production and supply the best service to domestic and overseas customers wholeheartedly for ODM Boundary Load Break Switch Manufacturers – CJ19 Capacitor Switching Contactor – Changan Group , The product will supply to all over the world, such as: kazakhstan, Japan, Philippines, Due to our good goods and services, we've received good reputation and credibility from local and international customers. If you will need more information and are interested in any of our solutions, be sure to feel free to contact us. We look forward to becoming your supplier in the near future.