We've been proud with the significant shopper fulfillment and wide acceptance due to our persistent pursuit of top of the range both of those on solution and repair for Surge Protection Device(Spd), Low Voltage Withdrawable Switchgear, Black Box Motion Control, Base within the small business concept of Top quality initially, we want to fulfill more and additional friends within the word and we hope provide the ideal solution and services to you.
ODM Arc-Fault Circuit Interrupter Factory – Electromagentic type 6KA RCBO CAL8-40M – Changan Group Detail:

Technical Data

Electrical Features

Mode Electromagnetic
Type

Rated current In

AC,A

6,8,10,13,16,20,25,32,40A

Poles 1P+N
Rated voltage Ue 230/240V~
Insulation voltage Ui 500V
Rated frequency 50/60Hz
Rated residual operating current(I△n) 30,100,300mA
Break time under I△n ≤0.1s
Rated breaking capacity 6,000A
Energy limiting class 3
Rated impulse withstand voltage(1.5/50) Uimp 4,000V
Dielectric test voltage at ind.Freq. for 1min 2kV
Pollution degree 2
Thermo-magnetic release characteristic B,C

Mechanical Features

Electrical life 4,000 Cycles
Mechanical life

Contact position indicator

10,000 Cycles

Yes

Protection degree IP20
Reference temperature for setting of thermal element 30℃
Ambient temperature (with daily average≤35℃) -5℃~+40℃
Storage temperature -25℃~+70℃

Installation

Terminal connection type

Terminal size top/bottom for cable

Cable/Pin-type busbar/U-type busbar

25mm2 18-3AWG

Terminal size top/bottom for busbar 25mm2 18-3AWG
Tightening torque 2.5Nm 22In-lbs
Mounting On DIN rail EN60715(35mm) by means of fast clip device
Connection Power supply in both directions

Combination accessories

Auxiliary contact Yes
Alarm contact Yes
Shunt release Yes
Over voltage protection Yes
Under voltage protection

Over/Under voltage protection

Yes

Yes

aaa


Product detail pictures:

ODM Arc-Fault Circuit Interrupter Factory –  Electromagentic type 6KA RCBO CAL8-40M – Changan Group detail pictures


Related Product Guide:

Our advancement depends over the highly developed devices, excellent talents and continually strengthened technology forces for ODM Arc-Fault Circuit Interrupter Factory – Electromagentic type 6KA RCBO CAL8-40M – Changan Group , The product will supply to all over the world, such as: Malaysia, Mauritius, Finland, We also have the strong ability of integration to supply our best service, and plan to build the warehouse in the different countries around the world, that will be more conveniently to service our customers.
  • Speaking of this cooperation with the Chinese manufacturer, I just want to say"well dodne", we are very satisfied.
    5 Stars By Leona from Guatemala - 2017.09.29 11:19
    After the signing of the contract, we received satisfactory goods in a short term, this is a commendable manufacturer.
    5 Stars By Norma from French - 2018.06.18 19:26
    Write your message here and send it to us