Famous Pre-Insulated Sleeve Manufacturers – CAC6 Series AC Contactor for 9-95A – Changan Group

Short Description:


Product Detail

Product Tags

Related Video

Feedback (2)

We not only will try our greatest to present fantastic expert services to each purchaser, but also are ready to receive any suggestion offered by our prospects for Acb Breaker, Led Power Indicator Circuit, Anchoring Bracket, The main goal of our company would be to live a satisfactory memory to all of the shoppers, and establish a long term company romantic relationship with customers and users all around the entire world.
Famous Pre-Insulated Sleeve Manufacturers – CAC6 Series AC Contactor for 9-95A – Changan Group Detail:

Scope Of Application

CAC6 series AC contactor (hereinafter referred to as contactor) is mainly used for AC 50 Hz,rated operating voltage is 380V, and AC-3 enables the circuit with rated working voltage of 380V and rated working current of 95A for remote connection and disconnection.In addition,it can form an electromagnetic starter with appropriate thermal overload relay to protect the circuit that may cause overload, and the contactor can be suitable for start and control AC motor frequently.
Standard GBT14048、GB2158 and IEC/EN 60947-4-1 and IEC/EN60947-5-1

Type Designation

Normal Operating Conditions

1. ambient temperature: ambient air temperature is -5℃~+40℃, and the average within 24 h does not exceed +35℃.
2. altitude: installation site not exceeding 2000m.
3. atmospheric conditions: when the maximum temperature is +40℃, the relative humidity of the air is not more than 50%, and a higher relative humidity can be allowed at a lower temperature, for example, at 20℃, the humidity can reach 90%. Special measures should be taken for occasional condensation due to temperature changes.
4. pollution grade: the pollution grade of the installation site is grade 3.
5. installation category: the installation category of contactor is III.
6. installation condition: Mounting face and vertical face inclination not more than ±5%
7. shock vibration: the product shall be installed and used without significant shaking, shock and vibration.

Structure Characteristics

1. The contactor has the characteristics of small size, light weight, low power consumption,high life, safety and reliability.
2. The contactor can add auxiliary contact group, air delay head, mechanical interlocking mechanism, thermal relay and other accessories to form a variety of derived products.
3. The contactor in addition to screw installation, can also be installed with 35mm、75mm type DIN rail.
4. The contactor control coil wiring terminal has A1、A2 mark, in which the A2 terminal has upper and lower two type, the user can choose according to the need.

Technical Data

1. Technical Specification.

Model No. CAC6-09 CAC6-12 CAC6-18 CAC6-25 CAC6-32 CAC6-40 CAC6-50 CAC6-65 CAC6-80 CAC6-95
Rated operational current 220V/380V AC-3 9 12 18 25 32 40 50 65 80 95
380V AC-4 3.3 5 7.7 8.5 12 18.5 24 28 37 44
Rated isolation voltage Ui(v) 690
Rated impulse withstand voltage (KV) 6 8
Rated conventional heating current 20 20 32 40 50 60 80 80 125 125
Power Controlled 3ph cage Motor 220V 2.2 3 4 5.5 7.5 11 15 18.5 22 25
380V 4 5.5 7.5 11 15 18.5 22 30 37 45
Operation frequency/h our Electrical life AC-3 1200 600
AC-4 300
Mechanical life 3600
Electrical life x104 operations AC-3 100 80 60
AC-4 20 15 10
Coil power (50Hz) Attracting V.A 70 70 70 110 110 200 200 200 200 200
Holding V.A 9 9 9.5 12.5 12.5 30.5 30.5 30.5 32.5 32.5
Power W 1.8~2.7 1.8~2.7 1.8~2.7 3~4 3~4 6~10 6~10 6~10 8~12 8~12
Mechanical life(104 operations) 1000 800 600
Flash-over distance 10 12
SCPD blending type “2” type
Rated short circuit limiting current 1kA/380V 3kA/380V 5kA/380V
Type of fuse NT00-16 NT00-20 NT00-25 NT00-32 NT00-50 NT00-63 NT00-63 NT00-80 NT00-100 NT00-125
Standard IEC60947-4-1 GB21518 GB/T 14048.4 JG/T7435

2. The contactor control coil operating voltage Us divided into: AC 50Hz,60Hz and 50/60Hz,24V、36V、110V、127V、220V、230V、240V、380V、400V、415V,and other specifications, users can choose according to demand;
3. Release characteristics: control voltage between 85%~110% Us can closed reliably;release voltage not more than 75% Us and not less than 20% Us;
4. The contactor has a pair of normally open and a pair of normally closed auxiliary contacts, in addition can be installed up to 4 pairs of auxiliary contact groups ,(it have a variety of often open and often closed combination), the basic parameters and performance of auxiliary contacts are shown in the table below;
5. Power consumption of contactor suction coil is shown in the table below;

Basic Parameters And Performance Of Auxiliary Contacts

Utilization category Rated operation voltage(V) Rated conventional heating current(A) Rated operation current(A) Control capacity
Close Open
AC-15 380 10 0.95 3600VA 360VA
AC-13 220 0.15 33W 33W

Power consumption of contactor suction coil

Model Start Holding
CAC6-9、12 70 9.0
CAC6-18 70 9.5
CAC6-25、32 110 12.5
CAC6-40、50、65 200 30.5
CAC6-80、95 200 32.5

6. Auxiliary Contact Type

Auxiliary Contact Type

Model Number of contacts Model Number of contacts
F4-22 2NO+2NC F4-20 2NO
F4-31 3NO+1NC F4-11 NO+NC
F4-13 1NO+3NC F4-02 2NC
F4-40 4NO
F4-04 4NC

7. Pneumatic Timer Type

Pneumatic Timer Type

Type Time-delay rang Auxiliary contacts number Type Time-delay rang Auxiliary contacts number
LA2-D20 0.1~3s NO+NC LA3-D20 0.1~3s NO+NC
LA2-D22 0.1~30s NO+NC LA3-D22 0.1~30s NO+NC
LA2-D24 10~180s NO+NC LA3-D24 10~180s NO+NC

Overall And Mounting Dimension 

Model Outline dimension Installation dimension Remarks
Amax Bmax Cmax a b
CAC6-9-18 47 76 89 35 56/50 screw installation, can also be installed with 35 mm type DIN rail.
CAC6-25-32 58 82 101 40/50 60
CAC6-40-65 77 129 123 59 106 except screw installation,can also be installed with 35mm、75mm type DIN rail.
CAC6-80-95 87 129 130 66 106

Installation, Use And Maintenance

1. Check the technical data (if the rated voltage, current, operating frequency, match the power.) of the coil before installation.
2. When installing, it should be installed in accordance with the prescribed installation conditions, and the terminal a1 mark of contact with the coils should be facing up, in line with human visual habits.
3. wiring screw should be tightened, check the wiring is correct, should be in the case of the main contact is not charged, the suction coil is first electrified several times, the test action is reliable before it can be put into use.
4. installation should be careful not let screw, washer, wire connector and other foreign bodies fall into the contactor, so as not to make the movable part stuck or cause short circuit accident.
5. If any abnormal noise is found during operating, it may be dirt on the iron core surface.Please clean the core surface.
6. During operating, all parts of the product should be inspected regularly, and the movable parts should be required to be free of blocking, the fasteners should not be loosened, and the parts should be replaced in time if they are damaged.
7. The contactor contacts due to arc burning black, burning hair phenomenon does not affect the use, not necessary to be filed, otherwise it will shorten the life of the contactor.

Ordering Instruction

1. Contactor name and model;
2. Coil rated operating voltage and frequency;
3. Order quantity;
4. If you need to order standard card details or accessories, it should be noted separately.
For sample: order CAC6-09 AC contactors, coil voltage 220V、50Hz, quantity 100 pcs.


Product detail pictures:


Related Product Guide:

Every single member from our higher effectiveness product sales staff values customers' requires and organization communication for Famous Pre-Insulated Sleeve Manufacturers – CAC6 Series AC Contactor for 9-95A – Changan Group , The product will supply to all over the world, such as: United States, Argentina, Benin, Our company is working by the operation principle of "integrity-based, cooperation created, people oriented, win-win cooperation". We hope we can have a friendly relationship with businessman from all over the world.
It is really lucky to meet such a good supplier, this is our most satisfied cooperation, I think we will work again!
5 Stars By Jonathan from US - 2018.05.22 12:13
The company can think what our think, the urgency of urgency to act in the interests of our position, can be said this is a responsible company, we had a happy cooperation!
5 Stars By Janet from Norwegian - 2018.09.29 13:24
Write your message here and send it to us