Famous Low VoltageH.R.C Fuse Manufacturers – CJ19 Series Capacitor Switching Contactor – Changan Group
Famous Low VoltageH.R.C Fuse Manufacturers – CJ19 Series Capacitor Switching Contactor – Changan Group Detail:
Description
Electric value: AC50/60Hz, up to 400V; Standard: IEC/EN 60947-4-1
Ambient temperature:-5℃~+40 ℃,
the average during 24 hours should not exceed +35 ℃; Altitude:≤2000m;
Atmosphere conditions: At mounting site,
relative humidity not exceed 50% at the max temperature of +40℃, higher relative humidity is allowable
under lower temperature. For example, RH could be 90% at +20℃,
special measures should be taken to occurrence of dews; Pollution degree: 3
Installation category: Ⅲ
Installation conditions :
the inclination between installation plane and vertical plane is within ± 5 °
Impact and shake: the products should locate
in the places where there are no obvious impact and shake.
Technical Specification
Standard |
IEC/EN60947-4-1 |
||||||
Model No. |
CJ19-25 |
CJ19-32 |
CJ19-43 |
CJ19-63 |
CJ19-80 |
CJ19-95 |
|
Rated Conventional Heating Current |
Ith (A) |
25 |
32 |
43 |
63 |
80 |
95 |
Rated Work Current |
415V/Ie (A) |
18 |
25 |
32 |
60 |
80 |
95 |
Capacitor Controlled |
220V/240V(Kvar) |
6 |
9 |
10 |
15 |
18 |
22 |
400V/440V(Kvar) |
12 |
18 |
20 |
30 |
36 |
40 |
|
Rated Insulation Voltage |
Ui(V) |
690 |
690 |
690 |
690 |
690 |
690 |
Rated Operation Voltage Electrial life(x103 ) |
Ue(V) |
400 |
400 |
400 |
400 |
400 |
400 |
Times |
120 |
120 |
120 |
100 |
100 |
100 |
|
Mechanical life(x103 ) |
Times |
3000 |
3000 |
3000 |
3000 |
3000 |
3000 |
Restrained Surge Capacity |
x Ie |
15 |
|||||
Auxiliary Contact |
Ith=10A |
AC-15 360VA;DC-13 33W |
|||||
Control Capacity |
COIL PARAMETERS
Coil Power(VA) |
Start-up |
76 |
110 |
110 |
230 |
230 |
230 |
Holding |
10 |
11 |
11 |
32 |
32 |
32 |
|
Rated Control Power |
Us(V) |
24,36,48,110,220,380 |
|||||
Pull time |
Ms |
12~22 |
15~24 |
15~24 |
20~26 |
20~35 |
20~35 |
Release time |
Ms |
4~12 |
5~19 |
5~19 |
8~12 |
6~20 |
6~20 |
Operation Range |
Pick-up |
(85%-110%)Us |
|||||
Drop-out |
(20%-75%)Us |
Model |
Amax |
Bmax |
Cmax |
Dmax |
E |
F |
Note |
CJ19-25 |
80 |
47 |
124 |
76 |
34/35 |
50/60 |
be fixed with 35mm din rail |
CJ19-32 |
90 |
58 |
132 |
86 |
40 |
48 |
|
CJ19-43 |
90 |
58 |
136 |
86 |
40 |
48 |
|
CJ19-63 |
132 |
79 |
150 |
- |
- |
- |
Not only fixed by screws but also couldbe fixed with 35mm and 75mm din rail |
CJ19-80~95 |
135 |
87 |
158 |
- |
- |
- |
Wiring and installation
5.1The connection terminals are protected through insulation cover, which is reliable and secure for installation and operation;
5.2For CJ19-25~43, screws are available for installation, as well as the DIN rail; for CJ19-63~95, 35mm or 75mm standard rail are available for installation.
Product detail pictures:
Related Product Guide:
With responsible good quality method, good status and excellent client services, the series of solutions produced by our company are exported to lots of countries and regions for Famous Low VoltageH.R.C Fuse Manufacturers – CJ19 Series Capacitor Switching Contactor – Changan Group , The product will supply to all over the world, such as: UK, Denver, Czech Republic, Insisting over the high-quality generation line management and prospects guide provider, we have made our resolution to offer our shoppers using the initially stage purchasing and soon after provider working experience. Preserving the prevailing helpful relations with our prospects, we even now innovate our product lists the many time to meet up with the brand new wants and stick to the latest trend of this business in Ahmedabad. We're ready to facial area the difficulties and make the transform to grasp many of the possibilities in international trade.