CS2 Motor Protection Circuit Breaker

Short Description:

Motor protector (also known as motor protector) is the function of comprehensive protection for motor, the motor start time, over-current, owe flow, locked-rotor, phase, short circuit, overvoltage, undervoltage, electric leakage (ground), three-phase imbalance, overheating, bearing wear, the rotor eccentricity, external fault, calls from the start, the time limit, the alarm or protection device.


Product Detail

Product Tags

Description

Electric value: AC690V, 32A, 80A;
Standard: IEC/EN 60947-2, IEC60947-4-1

Type Designation

CS2 SERIES MOTOR PROTECTION  (3)

Operating Condition

3.1 Temperature: -5 ℃~+40℃ ,average temperature in 24 hours not exceed +35 ℃
3.2 Altitude: not exceed 2000m
3.3 Air conditions:
At mounting site, relative humidity not exceed 50% at the max temperature of +40℃, higher
relative humidity is allowable under lower temperature,for example, RH could be 90% at +20℃
3.4 Pollution grade: Grade Ⅲ
3.5 Release grade: 10A(CS2-32) 10A(CS2-80)
3.6 Rated operational system: Continuous operational system
3.7 Mounting conditions:
The inclination between the mounting plane and the vertical plane shall not exceed 5 ° The product shall be installed and operated at a place without obvious shake, Impact and vibration.

Technical Specification

4.1 Protection property
Series No. Multiple of setting current Initial status Time Expected results Ambient temperature
1 1.05 Cold status t≥2h Non-tripping +20℃±2℃
2 1.20 Heat status (right after test.1) t<2h Tripping +20℃±2℃
3 1.50 Heat status (right after test.1) Tripping class 10A t<2min Tripping +20℃±2℃
        10 t<4min    
4 7.20 Cold status Tripping class 10A 2s<t≤10s Tripping +20℃±2℃

Phase failure protection properties

 

Series No.

Multiple of setting current  

Initial status

 

Time

Expected results Ambient temperature
  Any 2 phase The other phase        
1 1.0 0.9 Cold status

t≥2h

Non-tripping +20℃±2℃
2 1.15 0 Heat status

(right after test.1)

t <2h

Tripping +20℃±2℃

Temperature compensation properties

Series No. Multiple of setting current Initial status Time Expected results Ambient temperature
1 1.0 Cold status t≥2h Non-tripping

+40℃±2℃

2 1.2 Heat status (right after test.1) t<2h Tripping  +40℃±2℃
3 1.05 Cold status t≥2h Non-tripping

-5℃±2℃

4 1.3 Heat status (right after test.3) t<2h Tripping  -5℃±2℃
Model of overload relay  Code Rated current (A) Rated ultimate short-circuit breaking capacity Icu(kA) Rated service short-circuit breaking capacity Ics(kA) Standard rated power of three-phase motor (kW)
      230/240V 400/415V 660/690V 230/240V 400/415V 660/690V 230/240V 400/415V 660/690V
CS2-32

3201

0.1~0.16 100 100 100 100 100 100 - - -
 

3202

0.16~0.25 100 100 100 100 100 100 - - -
 

3203

0.25~0.4 100 100 100 100 100 100 - - -
 

3204

0.4~0.63 100 100 100 100 100 100 - - 0.37
 

3205

0.63~1 100 100 100 100 100 100 - - 0.55
 

3206

1~1.6 100 100 100 100 100 100 - - 1.1
 

3207

1.6~2.5 100 100 3 100 100 2.25 0.37 0.75 1.5
 

3208

2.5~4 100 100 3 100 100 2.25 0.75 1.5 3
 

3210

4~6.3 100 100 3 100 100 2.25 1.1 2.2 4
 

3214

6~10 100 100 3 100 100 2.25 2.2 4 7.5
 

3216

9~14 100 15 3 100 7.5 2.25 3 5.5 9
 

3220

13~18 100 15 3 100 7.5 2.25 4 9 11
 

3221

17~23 50 15 3 50 6 2.25 5.5 11 15
 

3222

20~25 50 15 3 50 6 2.25 5.5 11 18.5
 

3232

24~32 50 15 3 50 6 2.25 7.5 12.5 22
 CS2-80

8025

16~25 - 15 - - 7.5 - 5.5 11 -
 

8040

25~40 - 15 - - 7.5 - 11 22 -
 

8063

40~63 - 15 - - 7.5 - 15 33 -
 

8080

56~80 - 15 - - 7.5 - 22 45 -
CS2 MPCB_01
CS2 MPCB_02