Description
Application: remote making & breaking circuits; protect circuit from over-load when assembling with thermal over-load relay; frequent start-up and control of AC contactor;
Electric value: AC50/60Hz, 690V, up to 800A; Utilization category: AC-3, AC-4;
Altitude: ≤2000m;
Ambient temperature: -5℃~+40℃; Mounting category: Ⅲ;
Mounting conditions: inclination between the mounting plane and the vertical plane should not exceed ±5°;
Standard: IEC/EN 60947-4-1
Control Coil Voltage(AC Coil Operation)
Volts(VAC) |
24 |
36 |
42 |
48 |
110 |
127 |
220 |
230 |
240 |
380 |
415 |
440 |
480 |
500 |
600 |
|
Code |
50Hz |
B5 |
C5 |
D5 |
E5 |
F5 |
G5 |
M5 |
P5 |
U5 |
Q5 |
N5 |
R5 |
- |
S5 |
Y5 |
60Hz |
B6 |
- |
D6 |
E6 |
F6 |
G6 |
M6 |
- |
U6 |
Q6 |
- |
R6 |
T6 |
- |
- |
|
50/60Hz |
B7 |
- |
D7 |
E7 |
F7 |
- |
M7 |
P7 |
- |
Q7 |
N7 |
R7 |
- |
- |
- |
Control Coil Voltage(DC Coil Operation)
Volts(VDC) |
12 |
24 |
36 |
48 |
110 |
220 |
Code |
JD |
BD |
CD |
ED |
FD |
MD |
Technical Specification
Standard |
IEC/EN60947-4-1 |
||||||
Model No. |
CC1-115 |
CC1-150 |
CC1-185 |
CC1-225 |
CC1-265 |
CC1-330 |
|
Rated Conventional Heating Current |
Ith (A) |
200 |
200 |
275 |
275 |
315 |
380 |
Rated Voltage Ui(V) |
Ui(V) |
690 |
690 |
690 |
690 |
690 |
690 |
Rated Operation Current Ue=380/415V |
AC-3 Ie(A) |
115 |
150 |
185 |
225 |
265 |
330 |
AC-4 Ie(A) |
52 |
60 |
79 |
86 |
105 |
117 |
|
Power Controlled 3ph cage Motor AC-3 |
380/415V KW |
55 |
75 |
90 |
110 |
132 |
160 |
660/690V KW |
80 |
100 |
110 |
129 |
160 |
220 |
|
Electrial life (x103 operations) |
AC-3 |
600 |
600 |
300 |
300 |
300 |
300 |
AC-4 |
100 |
100 |
100 |
100 |
100 |
100 |
|
Mechanical life (x106 operations) |
6 |
6 |
3 |
3 |
3 |
3 |
|
Matched Fuse |
Size |
RT16-1 |
RT16-2 |
RT16-2 |
RT16-2 |
RT16-2 |
RT16-3 |
A |
200 |
225 |
315 |
315 |
355 |
450 |
|
Main circuit |
3P or 4P |
Standard |
IEC/EN60947-4-1 |
||||||
Model No. |
CC1-400 |
CC1-500 |
CC1-630 |
CC1-780 |
CC1-800 |
CC1-1000 |
|
Rated Conventional Heating Current |
Ith (A) |
460 |
580 |
850 |
1200 |
850 |
1200 |
Rated Voltage Ui(V) |
Ui(V) |
690 |
690 |
690 |
690 |
690 |
690 |
Rated Operation Current Ue=380/415V |
AC-3 Ie(A) |
400 |
500 |
630 |
780 |
800 |
1000 |
AC-4 Ie(A) |
138 |
147 |
188 |
240 |
195 |
320 |
|
Power Controlled 3ph cage Motor AC-3 |
380/415V KW |
200 |
250 |
335 |
400 |
400 |
500 |
660/690V KW |
280 |
335 |
450 |
475 |
475 |
560 |
|
Electrial life (x103 operations) |
AC-3 |
300 |
300 |
300 |
200 |
200 |
200 |
AC-4 |
100 |
100 |
100 |
50 |
50 |
50 |
|
Mechanical life (x106 operations)) |
3 |
3 |
3 |
2 |
3 |
2 |
|
Matched Fuse |
Size |
RT16-3 |
RT16-4 |
RT16-4 |
RT16-4 |
RT16-4 |
RT16-4 |
A |
500 |
630 |
800 |
1250 |
800 |
1250 |
|
Main circuit |
3P or 4P |
4. Terminal CModel | onnection
Cabling(Cu) |
Screw size | Tightening torque (N·m) | ||
Number of piece |
Cable Cross section(mm)2 |
Cu busbar Cross section(mm)2 | |||
CC1-115 |
1 |
70~90 |
- |
M6 |
3 |
CC1-150 |
1 |
70~90 |
- |
M8 |
6 |
CC1-185 |
1 |
95~150 |
- |
M8 |
6 |
CC1-225 |
1 |
95~150 |
- |
M10 |
10 |
CC1-265 |
1 |
120~185 |
- |
M10 |
10 |
CC1-330 |
1 |
185~240 |
- |
M10 |
10 |
CC1-400 |
1(2) |
240(150) |
30×5 |
M10 |
10 |
CC1-500 |
2 |
150~185 |
40×5 |
M10 |
10 |
CC1-630 |
2 |
185~240 |
50×5 |
M12 |
14 |
CC1-800 |
2 |
185~240 |
50×5 |
M12 |
14 |
Model |
A max |
B max |
C max |
CC1-115 |
163.5 |
162 |
171 |
CC1-150 |
163.5 |
170 |
171 |
CC1-185 |
168.5 |
174 |
181 |
CC1-225 |
168.5 |
197 |
181 |
CC1-265 |
201.5 |
203 |
213 |
CC1-330 |
213 |
206 |
219 |
CC1-400 |
213 |
206 |
219 |
CC1-500 |
233 |
238 |
232 |
CC1-630/800 |
309 |
304 |
255 |
Product detail pictures:
![China Best Thermal Overload Relay Factory – CC1 Series AC Contactor for 115-1000A – Changan Group detail pictures](https://cdn.globalso.com/changan-electric/CC1-400.jpg)
![China Best Thermal Overload Relay Factory – CC1 Series AC Contactor for 115-1000A – Changan Group detail pictures](https://cdn.globalso.com/changan-electric/CC1-225.jpg)
![China Best Thermal Overload Relay Factory – CC1 Series AC Contactor for 115-1000A – Changan Group detail pictures](https://cdn.globalso.com/changan-electric/CC1-630.jpg)
![China Best Thermal Overload Relay Factory – CC1 Series AC Contactor for 115-1000A – Changan Group detail pictures](https://cdn.globalso.com/changan-electric/CC1-780.jpg)
Related Product Guide:
Our pursuit and firm aim should be to "Always fulfill our buyer requirements". We carry on to produce and structure top-quality excellent solutions for equally our aged and new consumers and accomplish a win-win prospect for our consumers as well as us for China Best Thermal Overload Relay Factory – CC1 Series AC Contactor for 115-1000A – Changan Group , The product will supply to all over the world, such as: Durban, Iceland, Guyana, After years' creating and developing, with the advantages of trained qualified talents and rich marketing experience, outstanding achievements were gradually made. We get good reputation from the customers due to our good solutions quality and fine after-sale service. We sincerely wish to create a more prosperous and flourishing future together with all the friends home and abroad!
![5 Stars](https://www.changan-electric.com/admin/img/star-icon.png)
This is the first business after our company establish, products and services are very satisfying, we have a good start, we hope to cooperate continuous in the future!
![5 Stars](https://www.changan-electric.com/admin/img/star-icon.png)