Gaining client pleasure is our company's aim without end. We are going to make excellent efforts to create new and top-quality goods, meet your special requirements and provide you with pre-sale, on-sale and after-sale companies for Vacuum Circuit Breaker, Outdoor Current Transformer, Pre-Insulated Bimetal Lug, In addition, we would properly tutorial the purchasers about the application techniques to adopt our items plus the way to select appropriate materials.
China Best Prefabricated Substation Manufacturer – CS2 Series Motor Protection Circuit Breaker – Changan Group Detail:

Description

Electric value: AC690V, 32A, 80A;
Standard: IEC/EN 60947-2, IEC60947-4-1

Type Designation

CS2 SERIES MOTOR PROTECTION  (3)

Operating Condition

3.1 Temperature: -5 ℃~+40℃ ,average temperature in 24 hours not exceed +35 ℃
3.2 Altitude: not exceed 2000m
3.3 Air conditions:
At mounting site, relative humidity not exceed 50% at the max temperature of +40℃, higher
relative humidity is allowable under lower temperature,for example, RH could be 90% at +20℃
3.4 Pollution grade: Grade Ⅲ
3.5 Release grade: 10A(CS2-32) 10A(CS2-80)
3.6 Rated operational system: Continuous operational system
3.7 Mounting conditions:
The inclination between the mounting plane and the vertical plane shall not exceed 5 ° The product shall be installed and operated at a place without obvious shake, Impact and vibration.

Technical Specification

4.1 Protection property

Series No. Multiple of setting current Initial status Time Expected results Ambient temperature
1 1.05 Cold status t≥2h Non-tripping +20℃±2℃
2 1.20 Heat status (right after test.1) t<2h Tripping +20℃±2℃
3 1.50 Heat status (right after test.1) Tripping class 10A t<2min Tripping +20℃±2℃
        10 t<4min    
4 7.20 Cold status Tripping class 10A 2s<t≤10s Tripping +20℃±2℃

Phase failure protection properties

 

Series No.

Multiple of setting current  

Initial status

 

Time

Expected results Ambient temperature
  Any 2 phase The other phase        
1 1.0 0.9 Cold status

t≥2h

Non-tripping +20℃±2℃
2 1.15 0 Heat status

(right after test.1)

t <2h

Tripping +20℃±2℃

Temperature compensation properties

Series No. Multiple of setting current Initial status Time Expected results Ambient temperature
1 1.0 Cold status t≥2h Non-tripping

+40℃±2℃

2 1.2 Heat status (right after test.1) t<2h Tripping  +40℃±2℃
3 1.05 Cold status t≥2h Non-tripping

-5℃±2℃

4 1.3 Heat status (right after test.3) t<2h Tripping  -5℃±2℃
Model of overload relay  Code Rated current (A) Rated ultimate short-circuit breaking capacity Icu(kA) Rated service short-circuit breaking capacity Ics(kA) Standard rated power of three-phase motor (kW)
      230/240V 400/415V 660/690V 230/240V 400/415V 660/690V 230/240V 400/415V 660/690V
CS2-32

3201

0.1~0.16 100 100 100 100 100 100 - - -
 

3202

0.16~0.25 100 100 100 100 100 100 - - -
 

3203

0.25~0.4 100 100 100 100 100 100 - - -
 

3204

0.4~0.63 100 100 100 100 100 100 - - 0.37
 

3205

0.63~1 100 100 100 100 100 100 - - 0.55
 

3206

1~1.6 100 100 100 100 100 100 - - 1.1
 

3207

1.6~2.5 100 100 3 100 100 2.25 0.37 0.75 1.5
 

3208

2.5~4 100 100 3 100 100 2.25 0.75 1.5 3
 

3210

4~6.3 100 100 3 100 100 2.25 1.1 2.2 4
 

3214

6~10 100 100 3 100 100 2.25 2.2 4 7.5
 

3216

9~14 100 15 3 100 7.5 2.25 3 5.5 9
 

3220

13~18 100 15 3 100 7.5 2.25 4 9 11
 

3221

17~23 50 15 3 50 6 2.25 5.5 11 15
 

3222

20~25 50 15 3 50 6 2.25 5.5 11 18.5
 

3232

24~32 50 15 3 50 6 2.25 7.5 12.5 22
 CS2-80

8025

16~25 - 15 - - 7.5 - 5.5 11 -
 

8040

25~40 - 15 - - 7.5 - 11 22 -
 

8063

40~63 - 15 - - 7.5 - 15 33 -
 

8080

56~80 - 15 - - 7.5 - 22 45 -

CS2 MPCB_01
CS2 MPCB_02


Product detail pictures:

China Best Prefabricated Substation Manufacturer –  CS2 Series Motor Protection Circuit Breaker – Changan Group detail pictures

China Best Prefabricated Substation Manufacturer –  CS2 Series Motor Protection Circuit Breaker – Changan Group detail pictures


Related Product Guide:

Our products are widely recognized and trusted by users and can meet continuously developing economic and social needs for China Best Prefabricated Substation Manufacturer – CS2 Series Motor Protection Circuit Breaker – Changan Group , The product will supply to all over the world, such as: French, Liverpool, Czech Republic, we've got all day online sales to make sure the pre-sale and after-sale service in time. With all these supports, we can serve every customer with quality product and timely shipping with highly responsibility. Being a young growing company, we might not the best, but we are trying our best to be your good partner.
  • This manufacturer can keep improving and perfecting products and service, it is in line with the rules of market competition, a competitive company.
    5 Stars By Doreen from Rwanda - 2017.07.28 15:46
    Products and services are very good, our leader is very satisfied with this procurement, it is better than we expected,
    5 Stars By Katherine from Rwanda - 2018.06.05 13:10
    Write your message here and send it to us