Description
Electric value: AC 50/60Hz, 690V, 0.1A~630A; Tripping class: 10A;
Mounting version:
a.Plug-in: Available for CR2-03,13,23,33,43;
b.Independent: Available for CR2-53, 63; Standard: IEC/EN 60947-4-1
Type Designation
Feature
3.1 3-phase bimetal
3.2Continuously readjustable current settings
3.3Temperature compensation
3.4Tripping indicator
3.5Test button
3.6Stop button
3.7Manual and automatic reset button
Electrically separated 1N/O plus 1N/C contact
Technical Specification
Item |
Series No. |
I/In |
Operating time Tp |
Test condition | |
Overload protection | 1 | 1.05 | >2 h | Start from cold status | |
2 |
1.2 |
≤2h |
Start from heat status, right after item No.1 | ||
3 |
1.5 |
≤2min |
Start from heat status, right after item No.1 | ||
4 | 7.2 | 2s<Tp≤10s | Startfromcoldstatus | ||
Phase failure protection | 5 | Any two phases | Another phase | >2 h | Start from cold status |
1.0 |
0.9 |
||||
6 |
1.15 |
0 |
≤2 h |
Start from heat status, right after item No.5 |
Assembly with contactor
Model of overload relay | Code | Rated current (A) | Recommended fuse type (RT16 is recommended) | Contactor Matched | |
aM |
gG |
||||
CR2-03 |
0301 |
0.1~0.16 |
0.25 |
2 |
CC1-09K CC1-12K |
0302 |
0.16~0.25 |
0.5 |
2 |
||
0303 |
0.25~0.4 |
1 |
2 |
||
0304 |
0.4~0.63 |
1 |
2 |
||
0305 |
0.63~1 |
2 |
4 |
||
0306 |
1~1.6 |
2 |
4 |
||
0307 |
1.6~2.5 |
4 |
6 |
||
0308 |
2.5~4 |
6 |
10 |
||
0310 |
4~6 |
8 |
16 |
||
0312 |
5.5~8 |
12 |
20 |
||
0314 |
7~10 |
12 |
20 |
||
0316 |
9~13 |
16 |
25 |
||
CR2-13 |
1301 |
0.1~0.16 |
0.25 |
2 |
CC1-09 CC1-12 CC1-18 CC1-25 CC1-32 |
1302 |
0.16~0.25 |
0.5 |
2 |
||
1303 |
0.25~0.4 |
1 |
2 |
||
1304 |
0.4~0.63 |
1 |
2 |
||
1305 |
0.63~1 |
2 |
4 |
||
1306 |
1~1.6 |
2 |
4 |
||
1307 |
1.6~2.5 |
4 |
6 |
||
1308 |
2.5~4 |
6 |
10 |
||
1310 |
4~6 |
8 |
16 |
||
1312 |
5.5~8 |
12 |
20 |
||
1314 |
7~10 |
12 |
20 |
||
1316 |
9~13 |
16 |
25 |
||
1321 |
12~18 |
20 |
35 |
||
1322 |
17~25 |
25 |
50 |
||
CR2-23 |
2353 |
23~32 |
40 |
63 |
CC1-32 |
2355 |
30~40 |
40 |
80 |
||
CR2-33 |
3353 |
23~32 |
40 |
63 |
CC1-40 CC1-50 CC1-65 CC1-80 CC1-95 |
3355 |
30~40 |
40 |
100 |
||
3357 |
37~50 |
63 |
100 |
||
3359 |
48~65 |
63 |
100 |
||
3361 |
55~70 |
80 |
125 |
||
3363 |
63~80 |
80 |
125 |
||
3365 |
80~93 |
100 |
160 |
||
CR2-43 |
4366 |
80~104 |
125 |
200 |
CC1-115 CC1-150 |
4367 |
95~120 |
125 |
224 |
||
4368 |
110~150 |
160 |
250 |
||
CR2-53 |
5369 |
80~125 |
125 |
200 |
CC1-115 CC1-185 CC1-150 CC1-225 |
5370 |
100~160 |
160 |
250 |
||
5371 |
125~200 |
200 |
315 |
||
CR2-63 |
6372 |
160~250 |
250 |
400 |
CC1-185 CC1-400 CC1-225 CC1-500 CC1-265 CC1-630 CC1-330 |
6373 |
200~315 |
315 |
500 |
||
6374 |
250~400 |
400 |
630 |
||
6375 |
315~500 |
500 |
800 |
||
6376 |
400~630 |
630 |
800 |
Product detail pictures:
Related Product Guide:
We stick to our enterprise spirit of "Quality, Performance, Innovation and Integrity". We purpose to create a lot more price for our prospects with our rich resources, innovative machinery, experienced workers and great products and services for China Best Electric Motor Starter Factories – CR2 Series Thermal Overload Relay – Changan Group , The product will supply to all over the world, such as: Juventus, Sevilla, Nepal, Based on products with high quality, competitive price, and our full range service, we have accumulated professional strength and experience, and we have built up a very good reputation in the field. Along with the continuous development, we commit ourselves not only to the Chinese domestic business but also the international market. May you moved by our high quality products and passionate service. Let's open a new chapter of mutual benefit and double win.
By Edith from Swaziland - 2017.01.28 18:53
We feel easy to cooperate with this company, the supplier is very responsible, thanks.There will be more in-depth cooperation.
By Hellyngton Sato from Angola - 2017.09.28 18:29