CC1 AC Contactor for 115-1000A
Description
Application: remote making & breaking circuits; protect circuit from over-load when assembling with thermal over-load relay; frequent start-up and control of AC contactor;
Electric value: AC50/60Hz, 690V, up to 800A; Utilization category: AC-3, AC-4;
Altitude: ≤2000m;
Ambient temperature: -5℃~+40℃; Mounting category: Ⅲ;
Mounting conditions: inclination between the mounting plane and the vertical plane should not exceed ±5°;
Standard: IEC/EN 60947-4-1
Control Coil Voltage(AC Coil Operation)
Volts(VAC) |
24 |
36 |
42 |
48 |
110 |
127 |
220 |
230 |
240 |
380 |
415 |
440 |
480 |
500 |
600 |
|
Code |
50Hz |
B5 |
C5 |
D5 |
E5 |
F5 |
G5 |
M5 |
P5 |
U5 |
Q5 |
N5 |
R5 |
- |
S5 |
Y5 |
60Hz |
B6 |
- |
D6 |
E6 |
F6 |
G6 |
M6 |
- |
U6 |
Q6 |
- |
R6 |
T6 |
- |
- |
|
50/60Hz |
B7 |
- |
D7 |
E7 |
F7 |
- |
M7 |
P7 |
- |
Q7 |
N7 |
R7 |
- |
- |
- |
Control Coil Voltage(DC Coil Operation)
Volts(VDC) |
12 |
24 |
36 |
48 |
110 |
220 |
Code |
JD |
BD |
CD |
ED |
FD |
MD |
Technical Specification
Standard |
IEC/EN60947-4-1 |
||||||
Model No. |
CC1-115 |
CC1-150 |
CC1-185 |
CC1-225 |
CC1-265 |
CC1-330 |
|
Rated Conventional Heating Current |
Ith (A) |
200 |
200 |
275 |
275 |
315 |
380 |
Rated Voltage Ui(V) |
Ui(V) |
690 |
690 |
690 |
690 |
690 |
690 |
Rated Operation Current Ue=380/415V |
AC-3 Ie(A) |
115 |
150 |
185 |
225 |
265 |
330 |
AC-4 Ie(A) |
52 |
60 |
79 |
86 |
105 |
117 |
|
Power Controlled 3ph cage Motor AC-3 |
380/415V KW |
55 |
75 |
90 |
110 |
132 |
160 |
660/690V KW |
80 |
100 |
110 |
129 |
160 |
220 |
|
Electrial life (x103 operations) |
AC-3 |
600 |
600 |
300 |
300 |
300 |
300 |
AC-4 |
100 |
100 |
100 |
100 |
100 |
100 |
|
Mechanical life (x106 operations) |
6 |
6 |
3 |
3 |
3 |
3 |
|
Matched Fuse |
Size |
RT16-1 |
RT16-2 |
RT16-2 |
RT16-2 |
RT16-2 |
RT16-3 |
A |
200 |
225 |
315 |
315 |
355 |
450 |
|
Main circuit |
3P or 4P |
Standard |
IEC/EN60947-4-1 |
||||||
Model No. |
CC1-400 |
CC1-500 |
CC1-630 |
CC1-780 |
CC1-800 |
CC1-1000 |
|
Rated Conventional Heating Current |
Ith (A) |
460 |
580 |
850 |
1200 |
850 |
1200 |
Rated Voltage Ui(V) |
Ui(V) |
690 |
690 |
690 |
690 |
690 |
690 |
Rated Operation Current Ue=380/415V |
AC-3 Ie(A) |
400 |
500 |
630 |
780 |
800 |
1000 |
AC-4 Ie(A) |
138 |
147 |
188 |
240 |
195 |
320 |
|
Power Controlled 3ph cage Motor AC-3 |
380/415V KW |
200 |
250 |
335 |
400 |
400 |
500 |
660/690V KW |
280 |
335 |
450 |
475 |
475 |
560 |
|
Electrial life (x103 operations) |
AC-3 |
300 |
300 |
300 |
200 |
200 |
200 |
AC-4 |
100 |
100 |
100 |
50 |
50 |
50 |
|
Mechanical life (x106 operations)) |
3 |
3 |
3 |
2 |
3 |
2 |
|
Matched Fuse |
Size |
RT16-3 |
RT16-4 |
RT16-4 |
RT16-4 |
RT16-4 |
RT16-4 |
A |
500 |
630 |
800 |
1250 |
800 |
1250 |
|
Main circuit |
3P or 4P |
4. Terminal C
Model |
onnection
Cabling(Cu) |
Screw size |
Tightening torque (N·m) |
||
Number of piece |
Cable Cross section(mm)2 |
Cu busbar Cross section(mm)2 | |||
CC1-115 |
1 |
70~90 |
- |
M6 |
3 |
CC1-150 |
1 |
70~90 |
- |
M8 |
6 |
CC1-185 |
1 |
95~150 |
- |
M8 |
6 |
CC1-225 |
1 |
95~150 |
- |
M10 |
10 |
CC1-265 |
1 |
120~185 |
- |
M10 |
10 |
CC1-330 |
1 |
185~240 |
- |
M10 |
10 |
CC1-400 |
1(2) |
240(150) |
30×5 |
M10 |
10 |
CC1-500 |
2 |
150~185 |
40×5 |
M10 |
10 |
CC1-630 |
2 |
185~240 |
50×5 |
M12 |
14 |
CC1-800 |
2 |
185~240 |
50×5 |
M12 |
14 |
Model |
A max |
B max |
C max |
CC1-115 |
163.5 |
162 |
171 |
CC1-150 |
163.5 |
170 |
171 |
CC1-185 |
168.5 |
174 |
181 |
CC1-225 |
168.5 |
197 |
181 |
CC1-265 |
201.5 |
203 |
213 |
CC1-330 |
213 |
206 |
219 |
CC1-400 |
213 |
206 |
219 |
CC1-500 |
233 |
238 |
232 |
CC1-630/800 |
309 |
304 |
255 |