CJ19 Series Capacitor Switching Contactor
Description
Electric value: AC50/60Hz, up to 400V; Standard: IEC/EN 60947-4-1
Ambient temperature:-5℃~+40 ℃,
the average during 24 hours should not exceed +35 ℃; Altitude:≤2000m;
Atmosphere conditions: At mounting site,
relative humidity not exceed 50% at the max temperature of +40℃, higher relative humidity is allowable
under lower temperature. For example, RH could be 90% at +20℃,
special measures should be taken to occurrence of dews; Pollution degree: 3
Installation category: Ⅲ
Installation conditions :
the inclination between installation plane and vertical plane is within ± 5 °
Impact and shake: the products should locate
in the places where there are no obvious impact and shake.
Technical Specification
Standard |
IEC/EN60947-4-1 |
||||||
Model No. |
CJ19-25 |
CJ19-32 |
CJ19-43 |
CJ19-63 |
CJ19-80 |
CJ19-95 |
|
Rated Conventional Heating Current |
Ith (A) |
25 |
32 |
43 |
63 |
80 |
95 |
Rated Work Current |
415V/Ie (A) |
18 |
25 |
32 |
60 |
80 |
95 |
Capacitor Controlled |
220V/240V(Kvar) |
6 |
9 |
10 |
15 |
18 |
22 |
400V/440V(Kvar) |
12 |
18 |
20 |
30 |
36 |
40 |
|
Rated Insulation Voltage |
Ui(V) |
690 |
690 |
690 |
690 |
690 |
690 |
Rated Operation Voltage Electrial life(x103 ) |
Ue(V) |
400 |
400 |
400 |
400 |
400 |
400 |
Times |
120 |
120 |
120 |
100 |
100 |
100 |
|
Mechanical life(x103 ) |
Times |
3000 |
3000 |
3000 |
3000 |
3000 |
3000 |
Restrained Surge Capacity |
x Ie |
15 |
|||||
Auxiliary Contact |
Ith=10A |
AC-15 360VA;DC-13 33W |
|||||
Control Capacity |
COIL PARAMETERS
Coil Power(VA) |
Start-up |
76 |
110 |
110 |
230 |
230 |
230 |
Holding |
10 |
11 |
11 |
32 |
32 |
32 |
|
Rated Control Power |
Us(V) |
24,36,48,110,220,380 |
|||||
Pull time |
Ms |
12~22 |
15~24 |
15~24 |
20~26 |
20~35 |
20~35 |
Release time |
Ms |
4~12 |
5~19 |
5~19 |
8~12 |
6~20 |
6~20 |
Operation Range |
Pick-up |
(85%-110%)Us |
|||||
Drop-out |
(20%-75%)Us |
Model |
Amax |
Bmax |
Cmax |
Dmax |
E |
F |
Note |
CJ19-25 |
80 |
47 |
124 |
76 |
34/35 |
50/60 |
be fixed with 35mm din rail |
CJ19-32 |
90 |
58 |
132 |
86 |
40 |
48 |
|
CJ19-43 |
90 |
58 |
136 |
86 |
40 |
48 |
|
CJ19-63 |
132 |
79 |
150 |
- |
- |
- |
Not only fixed by screws but also could
be fixed with 35mm and 75mm din rail |
CJ19-80~95 |
135 |
87 |
158 |
- |
- |
- |
Wiring and installation
5.1The connection terminals are protected through insulation cover, which is reliable and secure for installation and operation;
5.2For CJ19-25~43, screws are available for installation, as well as the DIN rail; for CJ19-63~95, 35mm or 75mm standard rail are available for installation.