10KA MCB Mini Circuit Breaker CAB2-63H
Technical Data
Electrical Features
Rated current In | 1,2,3,4,5,6,8,10,13,16,20,25,32,40,50,63A |
Poles
Rated voltage Ue |
1P, 1P+N, 2P, 3P, 3P+N,4P
240/415V~ |
Insulation voltage Ui | 500V |
Rated frequency | 50/60Hz |
Rated breaking capacity | 1-40A 6,000A / 50-63A 4,500A |
Energy limiting class | 3 |
Rated impulse withstand voltage(1.5/50) Uimp | 4,000V |
Dielectric test voltage at ind. Freq. for 1 min | 2kV |
Pollution degree | 2 |
Thermo-magnetic release characteristic | B,C,D |
Mechanical Features
Electrical life | 4,000 Cycles |
Mechanical life
Contact position indicator |
10,000 Cycles
Yes |
Protection degree | IP20 |
Reference temperature for setting of thermal element | 30℃ |
Ambient temperature (with daily average≤35℃) | -5℃~+40℃ |
Storage temperature | -25℃~+70℃ |
Installation
Terminal connection type
Terminal size top/bottom for cable |
Cable/Pin-type busbar
25mm2 18-3AWG |
Terminal size top/bottom for busbar | 25mm2 18-3AWG |
Tightening torque | 2.5Nm 22In-Ibs |
Mounting | On DIN rail EN60715(35mm) by means of fast clip device |
Connection | Power supply in both directions |
Combination With Accessories
Auxiliary contact | Yes |
Alarm contact
Shunt release |
Yes
Yes |
Over/Under voltage release | Yes |
Write your message here and send it to us